• Id.Nr.: 229224-9
District heating tank FSN and FSN-E
• Maximum operating pressure on the heater side:
6 bar
• Maximum flow temperature on the heater side:
95 °C
• Maximum operating pressure on the domestic water side:
6 bar
• Average domestic water temperature:
60 °C
• Maximum pressure differential in the heating circuit:
1.2 bar (5 bar on demand)
• Recommended throughput volume:
300 l/h
• Domestic water connections:
1/2“
• Heater connections:
1/2“
• Dimensions:
Nominal capacity:
110l
height:
1,338 mm
width:
520 mm
depth:
520 mm
variable wall connection
15. District Heating System Connection
F
The regulation of the heating-up temperature via the remote heating circuit is done electrically and the
setting is fixed in the factory. An additionally installed temperature limiting device prevents overly high
back-flow temperatures. Changes to the settings may only be carried out following consultation with
the manufacturer.
Due to the high permissible pressure differential in the primary heating circuit it is not necessary to
regulate this pressure for the district heat storage tanks, however it must not exceed 1.2 bar. In order
to avoid malfunctions and the ingress of foreign bodies a dirt trap should be installed in the direction of
flow in the district heating supply pipe.
In all cases the connection of the district heat stor-
age tank should
be before the first radiator.
RADIATOR
FSN 110
Stair well
Flat