Assembly Instruction
FVM2
D
ATA
SHEET
02
D
ATA
SHEET
FVM2
Application: natural ventilation, SHEV, ferralux®-NSHEV
Surface or concealed mounting inside profi les
Locking plate (8 mm) on top or bottom mountable
Locking position selectable: right / left
Locking stroke selectable: s = 36 mm or 17 mm
Manual unlocking mechanism
Options
Special functions programmable
M-COM suitable internal Control Electronics and sequence control for drives S3 /S12
Star wiring
Current of the drives does not run over FVM2
Sequence control via communication wire
TECHNICAL DATA
U
N
Rated voltage
24V DC (19 V ... 28 V)
I
A
Cut-off current
~ 0,4 A
P
N
Rated power
10 W
I
D
Current of opening drives
non relevant
DC
Duty cycle
5 cycles (ED 30 % - ON: 3 min. / OFF: 7 min.)
Protection rating
IP 32
Ambient temperature range
-5 °C ... +60 °C
F
A
Pushing / Pulling force max.
~ 600 N
F
L
Breaking fore max.
~ 1000 N
t
Housing / Locking plate
stainless steel
Connecting cable
non-halogen, grey 3 x 0,5 mm², ~ 3 m
Speed
1,9 mm/s
s
Stroke
~ 36 mm (± 2) or 17 mm (± 1)
L
Dimensions
473 x 25 x 25 mm
Sound pressure level
≤ 70 dB (A)
ACCESSORIES
Hardware set
B23
Application
Surface mounting
on the
main/side closing edge
of the
window frame profi le of
inward
opening
windows. Adjustable
locking bolt for compensation of
the
profi le overlapp
FÜ 0 - 25 mm
NOTE
: Only one locking point!
Part.-No. 514081
Material / Finish
T-locking plate (aluminium)
Locking bracket VW
(stainless steel)
Feature / Equipment
1x T- locking plate
1x locking bracket B18
Locking plate
B24
Application
Locking plate 6 mm
alternative
to the locking plate 8 mm due
to limited rebate space.
Part.-No. 514066
Material / Finish
stainless steel
Feature / Equipment
37 x 30 x 6 mm
37
5,5
30
25
10
34
12,5
7
205
max. 1
13
2 x 17 ±1
473
11
7
s=36 ±2