Speed functions M1699
Speed internal1 M1930
Speed internal2 M1931
Speed internal3 M1932
Speed internal 4 M1933
Speed rem. min. M1936
Speed rem. max M1937
Default value: according to order data
Setting range: The adjustable speed range is indicated on the actuator name plate.
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: Press and enter ID, e.g.:
M1930
.
➥
Display indicates:
Speed internal1
Selection:
4.
Select via
Up ▲ Down ▼
:
→
▶ Speed internal1 M1930
→
▶ Speed internal2 M1931
→
▶ Speed internal3 M1932
→
▶ Speed internal 4 M1933
→
▶ Speed rem. min. M1936
→
▶ Speed rem. max M1937
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
6.
Press
Edit
.
➥
Display indicates:
-
Specialist (4) →
continue with step 7
-
in bottom row
Up ▲ Down ▼ Esc →
continue with step 11
Log on user
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
10. Press
Edit
.
Change value
11. Enter new value for speed via
Up ▲ Down ▼
.
Information: The adjustable speed range is shown in round brackets.
63
SAV 07.2 – SAV 16.2 / SARV 07.2 – SARV 16.2 Control unit: electronic (MWG)
ACV 01.2 HART
Commissioning (basic settings)