10.4.
HART address (slave address): set
HART address adaptation is only required for multidrop operation. Without multidrop
operation, address
0
must be set.
Customer settings M0041
HART M1238
Address M1253
Default value: 0
Setting range: 0 – 63
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Set HART address
3.
Select parameter either:
→
(by clicking through the menu)
→
or press and enter ID
M0098
(direct selection)
➥
Display indicates:
Address
4.
Press
Ok
.
➥
Display shows the set address.
5.
The bottom row of the display indicates:
→
Edit→
continue with step 6
→
Up ▲ Down ▼ →
continue with step 10
6.
Press
Edit
.
➥
Display indicates:
Observer (1)
7.
Select access level via
Up ▲ Down ▼
resulting in the following significations:
→
black triangle:
▶
= current setting
→
white triangle:
▷
= selection (not yet saved)
Information: Required access level:
Specialist (4)
or higher
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
Display shows the set address.
10. Enter new address via
Up ▲ Down ▼
.
Information: The address range is displayed in round brackets on the screen.
11. Confirm selection via
Save
.
➥
The HART address setting is complete.
10.5.
Output speed (internal): set
This setting is only required if an internally specified speed is set as speed source:
●
Sp. source...
=
Internal 1
/
Internal 2
/
Internal 3
/
Internal 4
●
Sp. source...
=
2 DigIn: "Internal (1-4)"
If the actuator is controlled via an external speed source, the internal speed values
described here will not have an impact on the operation behaviour.
For further information on setting the speed source refer to Manual (Operation and
Setting):
Customer settings M0041
62
SAV 07.2 – SAV 16.2 / SARV 07.2 – SARV 16.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACV 01.2 HART