7.5
Limit and torque switches
If different potentials are to be switched simultaneously, additional switches
must be used (not possible for torque switching).
7.6
Fitting the cover
After connection:
When connecting via terminals, refer to drawing, page 32.
When connecting via AUMA plug/ socket connector, refer to drawing,
page 33).
.
For AUMA plug/ socket connector, insert the socket carrier (2) into the
plug cover (1) and fasten with screws (04).
.
Clean sealing faces at the terminal cover or plug cover and the housing.
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
.
Replace terminal cover or plug cover and fasten bolts evenly crosswise.
.
Fasten cable glands with the specified torque to ensure the required
enclosure protection.
12
Multi-turn actuators SAI 6 – SAI 100 / SARI 6 – SARI 100
for valve automation Inside Containment in nuclear power plants
Operation instructions
Current type
Switch rating I
max
24 V
48 V
115 V
240 V AC
220 V DC
1-phase AC
current
Resistive load
–
–
–
2.5 A
Inductive load
–
–
–
1.5 A
DC current
Resistive load
4.0 A
3.0 A
1.0 A
0.4 A
Inductive load
2.5 A
1.8 A
0.5 A
0.2 A
Protective gas filling
Nitrogen
Change-over switch with
snap contact
gold-plated
Lifetime
100,000 switching cycles
Table 5: Technical data limit and torque switches
Figure F: Single switch