Operation and Display
FOX-EYE (indication LED)
Status indications: OK, end positions, faults and “Bluetooth connection active”.
Status
indication
Basic
at actuator
4 buttons and 1 LED are located below the hood.
Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve
Set end posi-
tions
Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve.
Set end posi-
tions
Smart
Via Bluetooth using AUMA Assistant
App or AUMA CDT software in the
latest version
●
Rotation speed
●
Type of seating for end positions,
Torque switching
●
Assignment of signal inputs and outputs
●
Fieldbus parameter (if fieldbus option has been selected).
●
etc.
Basic settings for operation:
Configura-
tion
For applications, safety and service, including:
●
Positioner
●
EMERGENCY behaviour
●
Torque by-pass
●
Failure behaviour
●
Signal configuration
●
etc.
Additional functions:
Monitoring key figures and measured values for preventive maintenance and consequently
increasing process safety. Limit values can be set. Deviations generate warning signals
which can be transmitted to the DCS via binary outputs or fieldbus.
Diagnostics
Temperature value within actuator
Key figures regarding lifetime of mechanics, grease, electron-
ics, and motor.
Actuator:
Method for identifying changes in torque requirement: Perform
reference operation and save torque as reference profile.
Define tolerance range. Perform comparative operation if re-
quired. Values outside tolerance initiate a signal which is
communicated as described above.
Actuator and valve:
In basic version, the actuator monitors and records further
figures and conditions. The generated fault and warning sig-
nals are saved within the event log. These signals can be
configured as requested. An overview in the AUMA Assistant
App or the CDT software shows all available fault/warning
signals with option to enter the details.
Further key figures:
Service conditions
Any position
Mounting position
≤
2,000 m above sea level
>
2 000 m above sea level on request
Installation altitude
–30 °C to +70 °C
Ambient temperature
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
IP67
Standard:
Enclosure protection according to
EN 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Duration of continuous immersion in water: Max. 96 hours
●
Up to 10 operations during continuous immersion
●
Modulating duty is not possible during continuous immersion
Option:
Pollution degree 4 (when closed), pollution degree 2 (internal)
Pollution degree according to IEC
60664-1
2 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
40
PROFOX / PF-M25 – PF-M100
Technical data
Profibus DP