7.1.1.
End position CLOSED: set
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Electrical connection and commissioning must be carried out exclusively by
suitably qualified personnel if circuit is live.
→
Do not touch any cables.
1.
Remove cover from actuator.
2.
Operate in direction CLOSE via push button until complete valve closing.
➥
The operation in direction CLOSE is signalled by the LED flashing in red.
3.
Once the desired end position CLOSED has been reached, release the push
button .
➥
The LED continues flashing in blue for approx. 10 seconds. This time span al-
lows for end position setting.
4.
While LED is flashing in blue, hold down push button
for at least two seconds
until the LED is illuminated in red.
➥
The end position CLOSED setting has been successfully completed.
24
PROFOX / PF-M25 – PF-M100
Commissioning
Profibus DP