Figure 22: Operation in direction OPEN
During operation in direction CLOSE, only the yellow position indication disc is
moving. The white end position indication ring remains in end position OPEN.
After having changed the end position OPEN, it is possible to open the position
indicator and readjust the white end position indication ring using a screw-
driver.
7.3.
Configuration of further parameters
Either the AUMA Assistant App or AUMA CDT software is required to use the
complete range of configuration options.
The user level defines which parameters are displayed or can be changed.
Information
For further information relating to user levels and passwords, please refer to
7.3.1.
Speed setting
The speeds are determined by the motor speed. The motor speed and thus the
actuator speed can be modified using the AUMA Assistant App or AUMA CDT.
Setting is made via a percentage within the range of 10 % to 100 %, whereby 100
% corresponds to the maximum actuator speed.
The speeds can be individually set for the following functions:
●
Standard speed for operations in directions OPEN and CLOSE and back
(parameter:
Motor speed 1
).
●
Alternative standard speed if different speeds are required for operation in dir-
ections OPEN and CLOSE or if continuous changes between two specified are
required (parameter:
Motor speed 2
).
●
Speeds for “Failure behaviour” and “EMERGENCY behaviour” functions:
-
for operation in direction CLOSE (parameter:
Mot. sp.FB+EMCY CL
)
-
for operation in direction OPEN (parameter:
Mot. sp.FB+EMCY OP
)
Variable speeds
for standard operations between directions OPEN and CLOSE and back: Defined
by an analogue input signal or fieldbus. The analogue input must be configured to
interpret this signal. For fieldbus operation, a respective field within the process
representation is available.
The speeds are programmed in %.
27
PROFOX / PF-M25 – PF-M100
Profibus DP
Commissioning