6 different users/user levels are available. User level (1), (2), (3), ... is indicated in
the top display row.
Figure 24: User level display (example user level 4)
Password
A specific password is assigned to each user level and allows different actions.
Table 14: User level and password
User levels and authorisations
Authorisation/password
User (user level)
Verify settings
No password required
Observer (1)
Change configuration parameters (low level)
Factory password: 000000
Operator (2)
Reserved for future use
Maintenance (3)
Change configuration parameters (high level)
e.g. type of seating, assignment of output contacts
Factory password: 000000
Specialist (4)
Service staff
Change configuration parameters (service level)
Service (5)
AUMA administrator
AUMA (6)
8.2.3.
Actuator operation from Remote
Operation mode Remote
For remote control, actuator operation mode must be set to Remote. The operation
mode can be modified via AUMA Assistant App or AUMA CDT software in “Operation
function” and “Set end positions”.
Default setting: Operation mode = Remote
Activate operation mode Remote via AUMA Assistant App:
→
Set parameter 555 (virtual selector switch) to REMOTE.
➥
Now, the actuator can be remote-controlled via fieldbus.
Change-over between
fieldbus control and
OPEN - CLOSE via I/O
signals
As standard, the actuator is supplied with fieldbus and binary signals. A binary input
is used to define which source is active, this means whether the actuator is controlled
via fieldbus or via I/O signals. It is not possible to use both sources to active
simultaneously. For this, the factory setting assigns the “I/O interface” signal to the
third binary input:
Not live (= 0 V) means that control is made from REMOTE via fieldbus.
Live (= 24 V) means that control is made from REMOTE via binary I/O interface.
Commands for the oper-
ation function
OPEN/CLOSE operation commands can be issued via fieldbus or a setpoint can be
sent for any position:
●
Setpoint control:
Command bit
Fieldbus SETPOINT
= 1 = Remote SETPOINT
The actuator reacts to the setpoint E1 transmitted via the fieldbus.
●
OPEN/CLOSE control:
Command bit
Fieldbus SETPOINT
= 0 = Remote OPEN-CLOSE
actuator can be operated via command bits in
Fieldbus OPEN
/
Fieldbus CLOSE
in direction OPEN or CLOSE.
EMERGENCY operation:
●
An EMERGENCY operation is initiated by the Fieldbus EMERGENCY command
bit.
●
The actuator moves to a predefined EMERGENCY position (i.e. end position
OPEN or end position CLOSED).
●
During EMERGENCY operation, the actuator does not react to other operation
commands such as Fieldbus/OPEN/Fieldbus/CLOSE or Fieldbus SETPOINT.
32
PROFOX / PF-M25 – PF-M100
Operation
Profibus DP