10.
Technical data
Information
The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com (please state the order number).
10.1.
Technical data fail safe unit
Weight
2)
Valve shaft
Valve attachment
Suitable part-turn actuator
Min.
torque
Fail safe oper-
ation in
s/90°
1)
Type
approx.
[kg]
Two-flat
Max. [mm]
Square
Max. [mm]
Cylindrical
Max. [mm]
Option
EN ISO 5211
Standard
EN ISO 5211
Possible operat-
ing times s/90°
Type
[Nm]
Configurable
in factory
63
22
22
25.4
F10
F07
5.6 to 32
SQ 05.2
150
9 to 34
FQM 05.1
66
22
22
25.4
F10
F07
5.6 to 32
SQ 07.2
300
8 to 26
FQM 07.1
137
36
36
50
F12
F10
11 to 63
SQ 10.2
600
15 to 54
FQM 10.1
140
36
36
50
F14
F12
22 to 63
SQ 12.2
1,200
13 to 39
FQM 12.1
Operating time increases when higher torque is required.
1)
The weights of SQ .2 actuators and AC .2 actuator controls must be added.
2)
Features and functions
FQM: Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
Standard:
Type of duty
FQMR: Intermittent duty S4 - 25 %, class C according to EN 15714-2
(not available in SIL version)
Option:
Refer to name plate
Permissible variation of mains voltage:
±
10 %
Permissible variation of mains frequency:
±
5 %
Mains voltage, mains frequency
24 V DC, current consumption: approx. 1 A
Permissible voltage variation: +20 %/–15 %
ESD input
Single switches (1 NC and 1 NO) for each end position: max. 0.1 A at 30 V DC
Output contact for fail safe function ready signal: max. 0.1 A at 30 V DC
All output signals must be supplied with the same potential.
Status signals
Adjustable between 80° and 96°
Swing angle
FQM = AUMA plug/socket connector with screw-type connection
FQMEx = Ex plug/socket connector with screw-type terminals (KP), max. 38 control ter-
minals / max. power supply 525 V AC
Standard:
Electrical connection
FQM = Terminals or crimp-type connection
FQMEx = Ex plug/socket connector with terminal blocks (KES)
Options:
Metric threads
Standard:
Threads for cable entries
Pg-threads, NPT-threads, G-threads
Option:
Terminal plan according to order number enclosed with delivery
Terminal plan
Coupling without bore
Standard:
Splined coupling for connection to
the valve shaft
Machined coupling with bore and keyway, square bore or bore with two-flats according to
EN ISO 5211
Option:
Dimensions according to EN ISO 5211 without spigot
Valve attachment
Service conditions
Indoor and outdoor use permissible
Use
Any position (for horizontal mounting position, a support is required)
Mounting position
≤
2 000 m above sea level
> 2 000 m above sea level on request
Installation altitude
–30 °C to +70 °C
Standard:
Ambient temperature
–60 °C to +60 °C
Option:
For exact version, refer to actuator name plate.
32
FQM 05.1 – FQM 12.1 / FQMEx 05.1 – FQMEx 12.1
Technical data