5.3.1.
KP/KPH electrical connection
5.3.1.1. Terminal compartment: open
Figure 14: Open terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Reducing socket
[5]
Cable gland
[6]
Flameproof frame
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
Information: The terminal compartment is designed in protection type Ex e
(increased safety). The interior of the flameproof enclosure (Ex d) of connected
housing remains closed when removing the cover [1].
2.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex e
approval) and enclosure protection IP.
The enclosure protection IP… stated on the name plate is only ensured if
suitable cable glands are used.
Figure 15: Name plate, example with enclosure protection IP68
3.
Seal unused cable entries with approved plugs suitable for the required protec-
tion type.
18
FQM 05.1 – FQM 12.1 / FQMEx 05.1 – FQMEx 12.1
Electrical connection