5.
Press
Ok
.
➥
Display indicates the current setting:
Limit
or
Torque
➥
The bottom row of the display indicates either:
-
Edit →
continue with step 6
-
Save →
continue with step 10
6.
Press
Edit
.
➥
Display indicates:
▶ Specialist (4)
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
The screen indicates the pre-set type of seating (
▶Limit
or
▶Torque
) by means
of a black triangle
▶
.
Change settings
10. Use
Up ▲ Down ▼
to select new setting.
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
11. Confirm selection via
Save
.
➥
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Esc
.
9.3.
Fieldbus address (slave address), baud rate, parity and monitoring time: set
Customer settings M0041
Modbus M0341
MD1 slave address M0247
MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address
=
247
MD2 slave address
=
247
Baud rate
=
Auto
Parity/stop bit
=
Even, 1 stop bit
Monitoring time
=
15
seconds
Information
Parameter
MD2 slave address
is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
9.4.
Switch compartment: open
The switch compartment must be opened to perform the following settings.
53
SQ 05.2 – SQ 14.2 / SQR 05.2 – SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
Commissioning (basic settings)