5.2.4.
Fieldbus terminal compartment: open
Figure 20: Open cover to fieldbus terminal compartment
[1]
Cover (fieldbus terminal compartment)
[2]
Screws for cover
[3]
O-ring
[4]
Cable entries for fieldbus cables
[5]
Blanking plug
The AUMA plug/socket connector is equipped with a connection board for connecting
the fieldbus cables. When removing the cover [1], the connection board is easily
accessible.
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→
Earth both operators and devices.
1.
Loosen screws [2] and remove cover [1].
2.
Insert cable glands suitable for fieldbus cables.
➥
The enclosure protection IP… stated on the name plate is only ensured if suit-
able cable glands are used.
Figure 21: Example: Name plate for enclosure protection IP68
3.
Seal unused cable entries with suitable plugs.
27
SQ 05.2 – SQ 14.2 / SQR 05.2 – SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
Electrical connection