![AUMA AC 01.2 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/auma/ac-01-2/ac-01-2_operation-instructions-manual_3016403045.webp)
For further information, please also refer to <Corrective action>.
Function check (S0009)
The
S0009
indication shows function check indications according to NAMUR
recommendation NE 107.
If an indication has occurred via the function check, the display shows
S0009
:
●
the number of indications occurred
●
a blinking triangle with a spanner after approx. 3 seconds
Figure 52: Function check
For further information, please also refer to <Corrective action>.
Maintenance required (S0010)
The
S0010
indication shows maintenance indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows
S0010
:
●
the number of indications occurred
●
a blinking square with an oilcan after approx. 3 seconds
Figure 53: Maintenance required
For further information, please also refer to <Corrective action>.
Failure (S0011)
The
S0011
indication shows the causes of the failure indication according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows
S0011
:
●
the number of indications occurred
●
a blinking circle with a cross after approx. 3 seconds
Figure 54: Failure
For further information, please also refer to <Corrective action>.
45
SQ 05.2 – SQ 14.2 / SQR 05.2 – SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
Indications