5.2.
SD electrical connection (AUMA plug/socket connector)
Figure 15: SD electrical connection
[1]
Terminal compartment (in cover)
[1A]
Cable entries for mains connection (power and control contacts)
[1B]
Cable entries for fieldbus cables
[2]
Socket carrier with screw-type terminals
Short description
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
SD version. For power and control cable connection, remove the AUMA plug/socket
connector and the socket carrier from terminal compartment. Removing the cover
is sufficient for connecting the fieldbus cables.
Technical data
Table 15:
Electrical connection via AUMA plug/socket connector
Control contacts
Power contacts
50 pins/sockets
6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50
U1, V1, W1, U2, V2, W2, PE
Designation
250 V
750 V
Connection voltage max.
16 A
25 A
Rated current max.
Screw connection, crimp-type (option)
Screw connection
Type of customer connection
2.5 mm
2
(flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
23
SQ 05.2 – SQ 14.2 / SQR 05.2 – SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU
Electrical connection