For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cables, cable glands, reducers, blanking plugs with a minimum
temperature range of +80 °C.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
●
For the connection of position transmitters, screened cables must be used.
Cable installation in ac-
cordance with EMC
Signal and fieldbus cables are susceptible to interference. Motor cables are
interference sources.
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●
Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
5.2.
Cable installation for wall bracket and control box
Figure 22: Example of cable installation for controls on wall bracket (without control
box)
[1]
Power supply, e.g. 3
∼
/PE/400V/50 Hz
[2]
Customer connection (XK) control contacts/signals
[3]
Motor connection/motor control
[4]
Feedback signals from actuator
[5]
Elektronischer Stellungsgeber RWG (Option) – eigensicherer Stromkreis
Wall bracket
The actuator controls are mounted separately from the actuator on a wall bracket.
●
The permissible cable length between actuator controls on wall bracket and
the actuator amounts to 100 m maximum.
●
We recommend using an AUMA cable set “LSW".
26
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
Electrical connection
ACExC 01.2
Содержание A 25.2
Страница 5: ...108 Index 111 Addresses 5 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 ACExC 01 2 Table of contents...
Страница 100: ...14 2 Actuator controls ACExC 01 2 KP KPH 100 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 102: ...14 3 Actuator controls AUMATIC ACExC 01 2 KES 102 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 104: ...14 4 Actuator controls ACExC 01 2 KT KM 104 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 106: ...14 5 ExC wall bracket 106 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 111: ...111...