INSTALLER
HIGH-TEMPERATURE ENERGY EFFICIENT HEAT PUMP
MANUAL
-
14
3.2.2 - Hydraulic connection : Heat Pump circuit
3.2.3 - Heat Pump and Pilot relief valve
3.2.4 - Desludging
When the heat pump is running at full power the fl ow rate
must be high enough to ensure that the temperature diff erence
between the outgoing and incoming water is no greater than 5°C
(take a temperature reading when the HRC
70
is in heating mode
and the system is fully functioning).
The hydraulic connection section between the Heat Pump and
the Pilot must be suffi
cient.
Using the tables below, determine the minimum inner diametre
of the connection piping needed depending on the distance
which separates the Heat Pump from the Pilot:
Heat pump model
17kW
20kW
25kW
Minimum nominal flow rate
1350 L/h
1550 L/h
1850 L/h
Maximium pressure
2.5 bar
2.5 bar
2.5 bar
minimum piping Ø
if distance* between HP and control < 15m
24/26
28/30
32/34
if distance* between HP and control < 25m
28/30
32/34
36/38
if distance* between HP and control < 50m
32/34
36/38
42/44
* distance comprises full circuit
Make sure that all sections of piping are fi tted with functional and
accessible air valves.
The hydrualic connection between the Heat Pump and the Pilot
can be made using steel, copper or PEX piping with a diametre of
at least 1’’.
The hydraulic kit must be fi tted using fl exible piping on the water
inlet and outlet points of the Heat Pump in order to prevent any
vibrations being transmitted to the heating system.
The Heat Pump and the Pilot are both fi tted with a pressure relief
valve.
The pressure relief valve on the Heat Pump sets the maximum
acceptable pressure in the installation (2.5 bars when hot). The
maximum service pressure on the Heat Pump must, consequently,
be lower than 2.5 bars.
Example : If the Heat Pump is positioned 5m below the Pilot , the
pressure reading on the Pilot would be 0.5 bars less than the
real pressure of the water in the Heat Pump. In this case, the
maximum pressure for the Pilot would be 2 bars.
Therefore it would be advisable to fi ll the heating circuit at
an intermediary pressure (between 1 and 1.5 bars).
In case of operating with boiler back-up these relief valves
MUST
be fi tted in addition to the ones which the boiler is already
equipped with.
The connections and evacuation conduits for the pressure relief
valves must be made from materials which are resistant to high
temperatures and corrosion.
PS
: Pilot pressure sensor
RV
: Pressure relief valve for Pilot, set at 3 bars
BRV
: Pressure relief valve for existing boiler
HPRV : Pressure relief valve for Heat Pump set at 2.5 bars
The Pilot has an integrated desludging function which collects
oxides, scale and other particles which become detached from
the inner walls of the heating circuit. The lower part of the system
is equipped with a sludge valve which should be briefl y activated
once a year (see § "Maintenance and Repairs").
For underfl oor heating installations, we would advise you to fi t
a settling tank, which will complement the actions taken by the
Pilot.
HRC Pilot
PS
RV
BPV
Existing
boiler
HRC Heat Pump
HPRV
See § ‘‘Setting the 4 speeds on the circulator pump’’ in appendix
1895709.
Содержание 151201
Страница 8: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 8 ...
Страница 76: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 76 HRC70 Pilot electrical schematic diagram ...
Страница 77: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 77 Please see following pages for key ...
Страница 80: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 80 HRC70 Pilot internal wiring diagram ...
Страница 81: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 81 Please see previous pages for key ...
Страница 83: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 83 NOTES ...