INSTALLER
HIGH-TEMPERATURE ENERGY EFFICIENT HEAT PUMP
MANUAL
-
58
A7.1 - HRC
70
Heat Pump, 17kW
A7.2 - HRC
70
Heat Pump, 20kW
A7.3 - HRC
70
Heat Pump, 25kW
When using a pure product that needs
to be diluted with water, mix the water,
anti-freeze and inhibitor together outside before
putting it into the installation.
RENDERING THE WARRANTY NULL & VOID
Any deterioration in the condition of the
appliances which is due to unsuitable
quality of fi lling water and / or corrosion in the
absence of treatment products as described
above and / or improper degassing of the
installation will result in the warranty being
rendered null and void.
A7 - Performance tables
Te
m
perature Te
m
perature
Air
Water
Max.
m
in.
Max.
m
in.
15°C
35°C
23.2
13.1
4.8
2.4
4.8
15°C
22.2
12.5
5.8
3
3.8
15°C
55°C
21.6
11.9
6.9
3.5
3.1
15°C
70°C
19.5
10.7
8.3
4.3
2.3
7°C
35°C
19.6
10.4
4.8
2.8
3.7
7°C
45°C
19.3
10.4
5.7
3.0
3.4
7°C
55°C
18.8
9.9
6.6
3.4
2.9
7°C
70°C
17.6
9.3
8
3.5
2.7
0°C
35°C
16.5
8.9
4.6
2.4
3.2
0°C
45°C
16.3
8.5
5.4
2.8
2.7
0°C
55°C
15.9
8.1
6.3
3.2
2.4
0°C
70°C
14.7
7.5
7.6
3.8
2
-7°C
35°C
14.2
7.4
4.5
2.3
3
-7°C
45°C
14
7.1
5.2
2.7
2.5
-7°C
55°C
13.5
6.8
6
3
2.2
-7°C
70°C
12.7
6.4
7.3
3.7
1.7
-15°C
35°C
11.8
6
4.2
2.2
2.8
-15°C
45°C
11.4
5.8
4.9
2.5
2.3
-15°C
55°C
11.1
5.6
5.6
2.9
2
-15°C
70°C *
10.8
5.5
7
3.5
1.5
-20°C
35°C
10
5.1
4
2.1
2.5
-20°C
45°C
9.8
5
4.7
2.4
2.1
-20°C
55°C
9.7
4.9
5.4
2.8
1.8
-20°C
70°C *
9.5
4.8
6.7
3.4
1.4
* When outdoor air temperatures are below -10°C, operating at 70°C is intermittent
Modulating ther
m
al
heating capacity (kW)
Electrical power
consu
m
ption (kW)
COP
Te
m
perature Te
m
perature
Air
Water
Max.
m
in.
Max.
m
in.
15°C
35°C
28.3
13.1
5.8
2.3
4.9
15°C
45°C
27.1
12.5
7.1
2.9
3.8
15°C
55°C
26.4
11.9
8.3
3.4
3.2
15°C
70°C
23.8
10.7
10.1
4.2
2.4
7°C
35°C
24
10.3
5.7
2.5
4.1
7°C
45°C
23.6
10.1
6.9
2.9
3.6
7°C
55°C
23
9.8
8
3.3
3
7°C
70°C
21.5
9.3
9.8
3.9
2.4
0°C
35°C
20.1
8.9
5.6
2.3
3.3
0°C
45°C
19.9
8.5
6.6
2.7
2.9
0°C
55°C
19.5
8.1
7.6
3.1
2.5
0°C
70°C
18
7.5
9.2
3.8
2.1
-7°C
35°C
17.3
7.4
5.4
2.2
3
-7°C
45°C
17.1
7.1
6.3
2.6
2.7
-7°C
55°C
16.4
6.8
7.2
2.9
2.3
-7°C
70°C
15.5
6.4
8.8
3.6
1.8
-15°C
35°C
14.4
6
5.1
2.1
2.8
-15°C
45°C
13.9
5.8
5.9
2.4
2.4
-15°C
55°C
13.5
5.6
6.8
2.8
2
-15°C
70°C *
13.2
5.5
8.5
3.4
1.6
-20°C
35°C
12.2
5.1
4.8
2
2.5
-20°C
45°C
12
5
5.6
2.3
2.1
-20°C
55°C
11.8
4.9
6.6
2.7
1.8
-20°C
70°C *
11.7
4.8
8.1
3.3
1.4
* When outdoor air temperatures are below -10°C, operating at 70°C is intermittent
Modulating ther
m
al
heating capacity (kW)
Electrical power
consu
m
ption (kW)
COP
•
Regularly check the Ph levels and % of
glycol in the installation
•
Never top up glycol in your installation
without measuring the Ph to check that the
drop in the glycol % is not due to deterioration
in the glycol.
•
When the Ph is acidic (<7) replace all of the
glycol after having drained and rinsed the
installation beforehand.
Te
m
perature Te
m
perature
Air
Water
Max.
m
in.
Max.
m
in.
15°C
35°C
19.8
8.9
4
1.6
4.9
15°C
45°C
18.9
8.5
4.9
2
3.9
15°C
55°C
18.4
8
5.8
2.4
3.2
15°C
70°C
16.6
7.2
7
2.9
2.4
7°C
35°C
16.7
7.2
4
1.7
4.3
7°C
45°C
16.5
6.5
4.8
1.8
3.6
7°C
55°C
16
6.1
5.6
2.1
3
7°C
70°C
14.6
5.7
6.7
2.4
2.3
0°C
35°C
14.1
6
3.9
1.6
3.3
0°C
45°C
13.9
5.8
4.6
1.9
2.7
0°C
55°C
13.2
5.5
5.3
2.1
2.4
0°C
70°C
12.2
5
6.3
2.6
2.1
-7°C
35°C
12.1
5
3.8
1.5
3
-7°C
45°C
11.6
4.8
4.4
1.8
2.5
-7°C
55°C
11.1
4.6
5
2
2.2
-7°C
70°C
10.5
4.3
6.1
2.5
1.7
-15°C
35°C
9.7
4.1
3.5
1.4
2.7
-15°C
45°C
9.4
3.9
4.1
1.7
2.3
-15°C
55°C
9.2
3.8
4.7
1.9
1.9
-15°C
70°C *
8.9
3.7
5.8
2.4
1.5
-20°C
35°C
8.3
3.5
3.4
1.4
2.5
-20°C
45°C
8.1
3.4
3.9
1.6
2.1
-20°C
55°C
8
3.3
4.6
1.9
1.8
-20°C
70°C *
7.9
3.3
5.6
2.3
1.4
* When outdoor air temperatures are below -10°C, operating at 70°C is intermittent
Modulating ther
m
al
heating capacity (kW)
Electrical power
consu
m
ption (kW)
COP
Содержание 151201
Страница 8: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 8 ...
Страница 76: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 76 HRC70 Pilot electrical schematic diagram ...
Страница 77: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 77 Please see following pages for key ...
Страница 80: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 80 HRC70 Pilot internal wiring diagram ...
Страница 81: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 81 Please see previous pages for key ...
Страница 83: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 83 NOTES ...