INSTALLER
HIGH-TEMPERATURE ENERGY EFFICIENT HEAT PUMP
MANUAL
-
42
Display
Nature of error
Solutions
• check condition of filter valve: clean filter
• check that HP flow rate is sufficient
• check that heating circulator pump is operating correctly
• check that the HP outgoing water sensor is correctly connected to the heat pump electronic circuit board
• check the HP outgoing water sensor cable
• check the ohmic value of the heat pump outgoing water sensor
• replace the heat pump outgoing water sensor
• check that the HP incoming water sensor is correctly connected to the heat pump electronic circuit board
• check the HP incoming water sensor cable
• check the ohmic value of the heat pump incoming water sensor
• replace the heat pump incoming water sensor
• check the heat pump air temperature sensor and evaporator sensor are operating correctly
• check that the 4way valve is operating correctly
• check that the compressor starter is not faulty
• check that the evaporator sensor is not covered in ice
• check that power grid is adapted to the heat pump's electricity requirements
• check that the power supply voltage does not drop below 200W during start-ups
• check for errors on compressor 1 starter (see § "Compressor start-up errors")
• check power supply voltage
• check power connections from electrical box to compressor 1 terminals
• check compressor 1 discharge
sensor
• check that power grid is adapted to the heat pump's electricity requirements
• check that the power supply voltage does not drop below 200W during start-ups
• check for errors on compressor 1 starter (see § "Compressor start-up errors")
• check power supply voltage
• check power connections from electrical box to compressor 2 terminals
• check compressor 2
discharge
sensor
• check that power grid is adapted to the heat pump's electricity requirements
• check that the power supply voltage does not drop below 200W during start-ups
• check for errors on compressor 1 starter (see § "Compressor start-up errors")
• check power supply voltage
• check power connections from electrical box to compressor 1 terminals
• check that power grid is adapted to the heat pump's electricity requirements
• check that the power supply voltage does not drop below 200W during start-ups
• check for errors on compressor 1 starter (see § "Compressor start-up errors")
• check power supply voltage
• check power connections from electrical box to compressor 2 terminals
• check that the swimming pool sensor is correctly connected to the HRC Pilot electronic circuit board
• check the swimming pool sensor cable
• check the ohmic value of the swimming pool sensor
• replace swimming pool sensor
• check position of outdoor sensor
• check values on both sensors (outdoor and HP air temp.)
ĺ
if one of the sensors is giving an erroneous reading, check condition of sensor
• check condition of cable and connections for each sensor
• replace defective sensor
• the water pressure in the heating circuit must be over 0.5 bars when cold.
• check that the heating circuit is watertight and repair any leaks.
• purge the air from the uppermost parts of the installation and the HRC Pilot.
• check that the heat pump pressure relief valve is watertight.
• check that the HRC Pilot pressure relief valve is watertight.
• check that the expansion vessel is big enough for the volume of the installation
• check that the fan is operating correctly (capacitor and electrical connections).
• check the condition of the finned heat exchanger surface and remove anything
which could be hampering the airflow through the rear grille (eg. leaves)
• if completely iced over, switch off the heat pump and let the ice melt. Spray with hot water if necessary.
• refrigerant leak, de-icing valve blocked or pressure reducing valve defect by a qualified professional
• check condition of filter valve
• check that heating network is properly purged
• check that HP circulator pump is running properly
• clean plated heat exchanger inlet
• discharge valve or 4-way valve malfunction
• check condition of filter valve
• check that heating network is properly purged
• check that HP circulator pump is running properly
• clean plated heat exchanger inlet
• discharge valve or 4-way valve malfunction
• check that the DHW sensor is correctly connected to the HRC Pilot electronic circuit board
• check the DHW sensor cable
• check the ohmic value of th DHW sensor
• replace DHW sensor
STARTER 1
ERR
STARTER 2
ERR
Smart starter 1 error
Smart starter 2 error
out Senso.
ERR
Outdoor temperature reading defective
Outdoor sensor and HP air temperature
sensor
show very different values
HP output
76.2
°
C
HP outgoing water overheating
defect > 75°C
Temperature read is displayed
hP output
ERR
HP outgoing water sensor defect
hP input
ERR
HP incoming water sensor defect
swim pool
ERR
Swimming pool sensor defect
evap. Senso.
ERR
Evaporator sensor malfunctioning
Prob comp1
Compressor 1 power supply fault
Prob comp2
Compressor 2 power supply fault
PRESSure
0.2
Insufficient water pressure
cuto. Lpre
HP low pressure
DHW TEMP
ERR
Swimming pool sensor defect
cuto. HPre 1
HP high pressure error
compressor 1
cuto. HPre 2
HP high pressure error
compressor 2
Содержание 151201
Страница 8: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 8 ...
Страница 76: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 76 HRC70 Pilot electrical schematic diagram ...
Страница 77: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 77 Please see following pages for key ...
Страница 80: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMP MANUAL 80 HRC70 Pilot internal wiring diagram ...
Страница 81: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 81 Please see previous pages for key ...
Страница 83: ... INSTALLER HIGH TEMPERATURE ENERGY EFFICIENT HEAT PUMPMANUAL 83 NOTES ...