INSTALLATION
30
EMX4i User Manual 710-14888-00C
Motor Connection
The EMX4i can be connected to the motor in-line or inside delta (also called
three-wire and six-wire connection). When connecting in inside delta, enter the
motor full load current (FLC) for parameter 1B. The EMX4i will automatically detect
whether the motor is connected in-line or inside delta and will calculate the correct
inside delta current level.
NOTE
If the starter is not correctly detecting the motor connection, use parameter
20F
Motor Connection
.
•
In-line installation
34
33
K1
K1
F1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
M
3
K1
Main contactor (strongly recommended)
F1
Fuses or circuit breaker (optional)
33, 34 Main contactor output
•
Inside delta installation
M
3
U1(1)
U2(4)
V1(2)
V2(5)
W1(3)
W2(6)
K1
F1
34
33
K1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
K1
Main contactor
F1
Fuses or circuit breaker (optional)
33, 34 Main contactor output