PROGRAMMABLE PARAMETERS
74
EMX4i User Manual 710-14888-00C
2O –
DC Brake Torque
Range:
20% - 100%
Default:
20%
Description:
Sets the amount of brake torque the EMX4i will use to slow the
motor.
2P –
DC Brake Time
Range:
0:01 - 0:30 (minutes:seconds)
Default:
1 second
Description:
Sets the duration for DC injection during a braking stop.
2Q –
Brake Current Limit
Range:
100% - 600% FLC
Default:
250%
Description:
Sets the current limit for soft brake.
2R –
Soft Brake Delay
Range:
400 - 2000 milliseconds
Default:
400 milliseconds
Description:
Sets the time the soft starter will wait after a stop signal is
received, before it begins to supply braking current to the motor.
Set to allow time for K1 and K2 to switch.
9.7
3 Motor Start/Stop-2
The parameters in this group control the operation of the secondary configuration
of the motor. Use the programmable input to select the active motor set.
Refer to
Secondary Motor Set
on page 60 for details.
3A –
Motor Full Load Current-2
Range:
Model dependent
Description:
Sets the secondary motor's full load current.
3B –
Motor kW-2
Range:
0 - 9999 kW
Default:
0
Description:
Sets the running power of the secondary motor, in kilowatts.
3C –
Start Mode-2
Options:
Constant Current (default)
Adaptive Control
Description:
Selects the soft start mode.
3D –
Start Ramp Time-2
Range:
0:01 - 3:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the total start time for an Adaptive Control start or the
ramp time for current ramp starting (from the initial current to
the current limit).