TROUBLESHOOTING
710-14888-00C EMX4i User Manual
123
Symptom
Probable Cause
After selecting Adaptive
Control the motor used
an ordinary start and/or
the second start was
different to the first.
•
The first Adaptive Control start is actually 'Constant
Current' so that the starter can learn from the motor
characteristics. Subsequent starts use Adaptive
Control.
PowerThrough does not
operate when selected.
•
The starter will trip on Lx-Tx Shorted on the first
start attempt after control power is applied.
PowerThrough will not operate if control power is
cycled between starts.
Parameter settings
cannot be stored.
•
Make sure you are saving the new value by pressing
the STORE button after adjusting a parameter
setting. If you press EXIT, the change will not be
saved. The EMX4i does not display a confirmation.
•
Check that the adjustment lock (parameter 10G) is
set to Read & Write. If the adjustment lock is set to
Read Only, settings can be viewed but not changed.
USB Full
•
The USB drive may not have enough free space
available for the selected function.
•
The file system on the USB drive may not be
compatible with the soft starter. The EMX4 supports
FAT32 file systems. The EMX4's USB functions are
not compatible with NTFS file systems.
USB Missing
A USB function has been selected in the menu, but the
product cannot detect a USB drive. Check that the USB
drive has been inserted in the port.
File Missing
A USB function has been selected in the menu, but the
required file cannot be found.
Save/Load Master Parameters uses a file called
Master_Parameters.par, at the top level of the USB
drive. For these functions to work correctly, do not move
or rename this file.
File Not Valid
A USB function has been selected in the menu, but the
file is not valid.
File Empty
A USB function has been selected in the menu and the
file has been found, but does not contain the expected
content.