background image

TC

AUBER INSTRUMENTS

2011.02

P7/8

TC

N

1

13 14

6

2

7

8

9

10

L

120VAC

Refrigerator

Fuse

SYL-2342

3

4

5

Bulb

+

-

Figure 11. A refrigerator connected to SYL-2342 directly

This is an example for beer fermentation. The refrigerator is driven by the 
internal relay of the controller directly. 

Please note that the internal relay 

output (terminals 7 and 8) is not powered by itself. 

A power supply 

must 

be used to drive the external relay. The refrigerator must consume less 
current than the internal relay’s maximum rating (7A at 240V AC and 10A at 
120V AC). The bulb (less than 100-300 W) is for heating. The example is 
setup to have the heater to turn on when temperature drops to below 60 °F 
and turns off at 64 °F. The refrigerator will turn on when temperature is above 
69 °F and turn off at 65 °F.

Set up for the controller

1) Hy = 2.0. Set both hysteresis band for heater and cooler to 2 degree.
2) COOL=9. Set the controller to cooling mode, no alarm suppression,  
Fahrenheit temperature unit display.
3) AT=0. Set the controller main output to on/off control mode for refrigerator 
compressor control
4) ALM2=62. Set the low limit alarm to 62 °F. Heater will be on at 60 °F 
(ALM2-Hy) and off at 64 °F (ALM2+Hy)
5) SV=67. Refrigerator will be on at 69 °F (SV+Hy) and off at 65 °F (SV-Hy).

SSR

L2

1 13 14 6

2

3

4

5

7

8

9

10

L1

240VAC

Heater

Fuse

SYL-2352

3

4

2

1

+

-

Figure 9. This is the essentially the same wiring example as 5.3, except the 
heater and controller are powered by 240V AC.  An alarm is not installed in 
this example.

RTD

R

R

W

5.4 Controlling the load via SSR, 240VAC example

5.5 Controlling a 24V valve

N

1 13 14 6

2

3

4

5

7

8

9

10

L

120VAC

Fuse

SYL-2342

Figure 10. SYL-2342 or SYL-2342P with thermocouple input. This is a typical 
wiring set up for a 24V gas, hot water valve, or a contactor with 24V coil 
voltage.

+

-

S

24VAC

Solenoid valve

5.6 Cooling and heating with the same controller

WWW.AUBERINS.COM

Содержание SYL-2342

Страница 1: ...ontrol output Ramp soak option SYL 2342 Relay contact output No SYL 2352 SSR control output No SYL 2342P Relay contact output Yes SYL 2352P SSR control output Yes All the models listed in table 1 are 1 16 DIN size with dual alarm outputs Table 1 Controller models 3 Terminal Wiring Figure 1 Wiring diagram 3 1 Sensor connection Please refer to table 3 for the input sensor type Sn setting codes The i...

Страница 2: ...t is not controlled by regulating amplitude of the voltage or current This is often referred as time proportional control e g If the cycle rate is set for 100 seconds a 60 output means controller will switch on the power for 60 seconds and off for 40 seconds 60 100 60 Almost all high power control systems use time proportional control because amplitude proportional control is too expensive and ine...

Страница 3: ...120 t Cycle time 2 125 2 for SSR 20 for relay See 4 6 Sn Input type 0 37 0 K type TC See 4 7 dP Decimal point position 0 3 0 See 4 8 P SL Display low limit 1999 9999 C or F 100 P SH Display high limit 1999 9999 C or F 2500 Pb Input offset 1999 4000 1999 9999 C or F 0 0 See 4 10 OP A Output mode 0 2 0 See 4 11 OUTL Output low limit 0 110 0 OUTH Output high limit 0 110 100 AL P Alarm output definiti...

Страница 4: ...At 1 or At 2 4 5 Control action explanations 4 5 1 PID Please note that because this controller uses fuzzy logic enhanced PID control software the definition of the control constants P I and d are different than that of the traditional proportional integral and derivative parameters In most cases the fuzzy logic enhanced PID control is very adaptive and may work well without changing the initial P...

Страница 5: ...imum ALM1 Hy 1 and Hy 2 to 9999 ALM2 to 1999 to stop its function 4 14 COOL for Celsius Fahrenheit Heating and Cooling Selection Parameter COOL is used to set the display unit heating or cooling and alarm suppression Its value is determined by the following formula COOL AX1 BX2 CX8 A 0 reverse action control mode for heating control 4 5 3 Manual mode Manual mode allows the user to control the outp...

Страница 6: ...cy within a fraction of a degree The SSR allows the heater to be switched at higher frequency for better stability It also has longer life time than the electromechanical relay A proper heat sink is needed when the SSR switches 8A of current For wiring a 240V heater please see 5 4 A 1 direct action control mode for cooling control B 0 without alarm suppressing when turned on or when set point chan...

Страница 7: ...esis band for heater and cooler to 2 degree 2 COOL 9 Set the controller to cooling mode no alarm suppression Fahrenheit temperature unit display 3 AT 0 Set the controller main output to on off control mode for refrigerator compressor control 4 ALM2 62 Set the low limit alarm to 62 F Heater will be on at 60 F ALM2 Hy and off at 64 F ALM2 Hy 5 SV 67 Refrigerator will be on at 69 F SV Hy and off at 6...

Страница 8: ...e parameter OUTL If this happens when using thermocouple sensor you can short terminal 4 and 5 with a copper wire If the display shows ambient temperature the thermocouple is defective If it still displays orAL check the input setting Sn to make sure it is set to the right thermocouple type If the Sn setting is correct the controller is defective For RTD sensors check the input setting first becau...

Отзывы: