background image

AUBER INSTRUMENTS

2011.02

P8/8

Quick Guide for SYL-2342, 2352

1. Wiring

1) Power to the controller. Connect the 85-260V AC power to terminals 9 and 
10.
2) Control output connection. Connect terminals 7 and 8 for output.
3) Sensor connection. For thermocouples, connect the positive wire to terminal 
4, the negative to terminal 5. For a three-wire RTD with standard DIN color 
code, connect the two red wires to terminals 3 and 4, and connect the white 
wire to terminal 5. For a two-wire RTD, connect the wires to terminals 4 and 5. 
Then, jump a wire between terminals 3 and 4. 

2. Set sensor type

Set Sn to 0 for a K type thermocouple (default), 5 for a J type thermocouple, 
and 21 for a Pt100 RTD.

3. Switching between automatic and manual mode

Set A-M=1 to active manual mode. Press the A/M key to switch between 
automatic and manual mode.

4.Changing the temperature scale from Fahrenheit to Celsius.

Change COOL from 10 to 2 (for heating mode).

5 Setting the controller for cooling control.

For cooling control, set COOL=11 to display Fahrenheit; set COOL=3 to 
display Celsius.

6. Setting target temperature (SV)

Press the 

 or 

 key once, and then release it. The decimal point on the 

lower right corner will start to flash. Press the 

 or

 key to change SV until 

the desired value is displayed. The decimal point will stop flashing after no key 
is pressed for 3 seconds. You can press the A/M key to move the flashing 
decimal point to the desired digit that needs to change. Then press the 

 or

 key to change SV starting from that digit.

7. Auto-tune

You can use the auto-tune function to determine the PID constants
automatically.
There are two ways to start auto-tuning:
1) Set At=2. It will start automatically after 10 seconds. 
2) Set At=1. Then during the normal operation, press the A/M key to start the 
auto-tune. 
The instrument will perform accurate artificial intelligence control after auto 
tuning is finished.

7 On/off mode

Set At=0 to active the on/off control mode.
Set the Hysteresis Band parameter Hy to be a desired value.

8. Error Message and trouble shooting

8.1 Display orAL

This is an input error message. The possible reasons are: the sensor is not 
connected correctly; the input setting is wrong type; or the sensor is defective.
In this case, the instrument terminates its control function automatically, and 
the output value is fixed according to the parameter OUTL. If this happens 
when using thermocouple sensor, you can short terminal 4 and 5 with a copper 
wire. If the display shows ambient temperature, the thermocouple is defective. 
If it still displays orAL, check the input setting, Sn, to make sure it is set to the 
right thermocouple type. If the Sn setting is correct, the controller is defective. 
For RTD sensors, check the input setting first because most controllers are 
shipped with the input set for thermocouples. Then check the wiring. The two 
red wires should be connected to terminals 3 and 4. The clear wire should be 
connected to terminal 5. 

8.2 No heating

When the controller output is set for relay output, the “ O U T ” LED is 
synchronized with output relay. If heat is not output when it is supposed to, 
check the OUT LED first. If it is not lit, the controller parameter settings are 
wrong. If it is on, check the external switching device (if the relay is pulled-in, or 
the SSR’s red LED is on). If the external switching device is on, then the 
problem is either the external switching device output, its wiring, or the heater. 

If the external switching device is not on, then the problem is either the 
controller output, or the external switch device.

8.3 Poor Accuracy

Please make sure calibration i s  done by immersing the probe in liquid. 
Comparing the reference in air is not recommended because response time of 
the sensor depends on its mass. Some of our sensors have response time 
>10 minutes in the air. When the error is larger than 5 °F, the most common 
problem is an improper connection between the thermocouple and the 
controller. The thermocouple needs to be connected directly to the controller 
unless a thermocouple connector and extension wire is used. Copper wire or 
a thermocouple extension wire with the wrong polarity connected on the 
thermocouple will cause the reading to drift more than 5 °F. 

8.4 On on/off mode, although hysteresis is set to 0.3, the unit is running 
5 degrees above and below.

If the Hy is very small and temperature changes very quickly, users will need 
to consider the delay of the cycle time (the parameter t). For example, if cycle 
time is 20 seconds, when the temperature passes the SV+Hy after the 
beginning of a 20 seconds cycle, the relay will not act until the start of the next 
cycle 20 seconds later. Users may change the cycle time to a smaller value, 
such as 2 seconds, to get better precision control.

WWW.AUBERINS.COM

 Auber Instruments

730 Culworth, Alpharetta, GA 30022

www.auberins.com 

e-mail: [email protected] Tel: 770-569-8420  

Содержание SYL-2342

Страница 1: ...ontrol output Ramp soak option SYL 2342 Relay contact output No SYL 2352 SSR control output No SYL 2342P Relay contact output Yes SYL 2352P SSR control output Yes All the models listed in table 1 are 1 16 DIN size with dual alarm outputs Table 1 Controller models 3 Terminal Wiring Figure 1 Wiring diagram 3 1 Sensor connection Please refer to table 3 for the input sensor type Sn setting codes The i...

Страница 2: ...t is not controlled by regulating amplitude of the voltage or current This is often referred as time proportional control e g If the cycle rate is set for 100 seconds a 60 output means controller will switch on the power for 60 seconds and off for 40 seconds 60 100 60 Almost all high power control systems use time proportional control because amplitude proportional control is too expensive and ine...

Страница 3: ...120 t Cycle time 2 125 2 for SSR 20 for relay See 4 6 Sn Input type 0 37 0 K type TC See 4 7 dP Decimal point position 0 3 0 See 4 8 P SL Display low limit 1999 9999 C or F 100 P SH Display high limit 1999 9999 C or F 2500 Pb Input offset 1999 4000 1999 9999 C or F 0 0 See 4 10 OP A Output mode 0 2 0 See 4 11 OUTL Output low limit 0 110 0 OUTH Output high limit 0 110 100 AL P Alarm output definiti...

Страница 4: ...At 1 or At 2 4 5 Control action explanations 4 5 1 PID Please note that because this controller uses fuzzy logic enhanced PID control software the definition of the control constants P I and d are different than that of the traditional proportional integral and derivative parameters In most cases the fuzzy logic enhanced PID control is very adaptive and may work well without changing the initial P...

Страница 5: ...imum ALM1 Hy 1 and Hy 2 to 9999 ALM2 to 1999 to stop its function 4 14 COOL for Celsius Fahrenheit Heating and Cooling Selection Parameter COOL is used to set the display unit heating or cooling and alarm suppression Its value is determined by the following formula COOL AX1 BX2 CX8 A 0 reverse action control mode for heating control 4 5 3 Manual mode Manual mode allows the user to control the outp...

Страница 6: ...cy within a fraction of a degree The SSR allows the heater to be switched at higher frequency for better stability It also has longer life time than the electromechanical relay A proper heat sink is needed when the SSR switches 8A of current For wiring a 240V heater please see 5 4 A 1 direct action control mode for cooling control B 0 without alarm suppressing when turned on or when set point chan...

Страница 7: ...esis band for heater and cooler to 2 degree 2 COOL 9 Set the controller to cooling mode no alarm suppression Fahrenheit temperature unit display 3 AT 0 Set the controller main output to on off control mode for refrigerator compressor control 4 ALM2 62 Set the low limit alarm to 62 F Heater will be on at 60 F ALM2 Hy and off at 64 F ALM2 Hy 5 SV 67 Refrigerator will be on at 69 F SV Hy and off at 6...

Страница 8: ...e parameter OUTL If this happens when using thermocouple sensor you can short terminal 4 and 5 with a copper wire If the display shows ambient temperature the thermocouple is defective If it still displays orAL check the input setting Sn to make sure it is set to the right thermocouple type If the Sn setting is correct the controller is defective For RTD sensors check the input setting first becau...

Отзывы: