background image

TC

AUBER INSTRUMENTS

2011.02

P6/8

4.17 Lock up the settings, field parameter “EP” and parameter “LocK”

To prevent the operator from changing the settings by accident, you can lock 
the parameter settings after initial setup. You can select which parameter can 
be viewed or changed by assigning one of the field parameters to it. Up to 8 
parameters can be assigned into field parameter EP1-EP8. The field 
parameter can be set to any parameter listed in Table 2, except parameter EP 
itself. When LocK is set to 0, 1, 2, and so on, only parameters or setting 
values of program defined in an EP can be displayed. This function can speed 
up parameter modification and prevent critical parameters (like input, output 
parameters) from being modified.
If the number of field parameters is less than 8, then define the first unused 
parameter as none. For example, if only ALM1 and ALM2 need to be modified 
by field operators, the parameter EP can be set as following:
LocK=0, EP1=ALM1, EP2=ALM2, EP3=nonE.
In this case, the controller will ignore the field parameters from EP4 to EP8. If 
field parameters are not needed after the instrument is initially adjusted, 
simply set EP1 to nonE.
Lock code 0, 1 and 2 will give the operator limited privileges to change some 
of the parameters that can be viewed. Table 5 shows the privileges 
associated with each lock code.

Table 5. LocK parameter

5. Wiring examples

5.1 Controlling the load directly with internal relay

N

1 13 14 6

2

3

4

5

7

8

9

10

L

120VAC

Heater

Fuse

SYL-2342

Figure 6. SYL-2342 or SYL-2342P control the heater directly by the
internal relay of the controller. The heater must consume less current than 
the internal relay’s maximum rating (7A at 240VAC and 10A at 120VAC).

LocK value

SV Adjustment

EP1-8 Adjustment Other parameters

0

Yes

Yes

Locked

1

Yes

No

Locked

2

No

Yes

Locked

3 and up

No

No

Locked

808

unlocked

SSR

N

1 13 14 6

2

3

4

5

7

8

9

10

L

120VAC

Heater

Fuse

SYL-2352

Alarm1 12V DC

3

4

2

1

5.3 Controlling the load via SSR

+

-

Figure 8. SYL-2352 or SYL-2352P with RTD input. This is a typical wiring for 
controlling the temperature of a tank of liquid with high precision. 

The RTD sensor can offer accuracy within a fraction of a degree . The SSR 
allows the heater to be switched at higher frequency for better stability. It also 
has longer life time than the electromechanical relay. A proper heat sink is 
needed when the SSR switches >8A of current. For wiring a 240V heater, 
please see 5.4.

A=1, direct action control mode for cooling control.
B=0, without alarm suppressing when turned on or when set point changes.
B=1, alarm suppressing at power up or set point changes.
C=0, display unit in ºC.
C=1, display unit in ºF.
The factory setting is A=0, B=1, C=1 (heating, with alarm suppression, display 
in Fahrenheit). Therefore,
COOL=0X1+1X2+1X8=10
To change from Fahrenheit to Celsius display, set COOL=2

4.15 Input digital filter “FILt”

If measurement input fluctuates due to noise, then a digital filter can be used 
to smooth the input. “FILt” may be configured in the range of 0 to 20. 
Stronger filtering increases the stability of the readout display, but causes 
more delay in the response to change in temperature. FILt=0 disables the 
filter.

4.16 Manual and Automatic Mode Selection “A-M”

Parameter A-M is for selecting automatic or manual control mode.
A-M=0, manual control mode
A-M=1, automatic control mode (either PID or On/off control)
A-M=2, automatic control mode, in this state manual operation is prohibited
This parameter functions differently for controllers with the ramp/soak function 
(see supplemental manual for details).

N

Contactor

TC

+

-

1

13 14

6

2

3

4

5

7

8

9

10

L

120VAC

Heater

Fuse

SYL-2342

Alarm1

12V 

DC

Alarm2

5.2 Controlling the load via external contactor

Figure 7. SYL-2342 or SYL-2342P with thermocouple input and external 
relay output. This is a typical wiring for oven and kiln.

Note: to limit the control temperature range instead of completely locking it, 
please refer to section 4.9.

RTD

R

R

W

+

-

WWW.AUBERINS.COM

Using the external contactor allows users to control higher power loads than 
the internal relay can handle. It is also easy to service. If the contacts of the 
relay wear out, it is more economical to replace them than to repair the 
controller. In this example, we assume the coil voltage of the contactor is the 
same as the voltage of the controller power supply. The voltage of power 
supply for alarm is 12V DC.  

Note: You don’t have to wire or set the alarm 

to control the temperature. It is just to show how the alarm can be wired. 

Содержание SYL-2342

Страница 1: ...ontrol output Ramp soak option SYL 2342 Relay contact output No SYL 2352 SSR control output No SYL 2342P Relay contact output Yes SYL 2352P SSR control output Yes All the models listed in table 1 are 1 16 DIN size with dual alarm outputs Table 1 Controller models 3 Terminal Wiring Figure 1 Wiring diagram 3 1 Sensor connection Please refer to table 3 for the input sensor type Sn setting codes The i...

Страница 2: ...t is not controlled by regulating amplitude of the voltage or current This is often referred as time proportional control e g If the cycle rate is set for 100 seconds a 60 output means controller will switch on the power for 60 seconds and off for 40 seconds 60 100 60 Almost all high power control systems use time proportional control because amplitude proportional control is too expensive and ine...

Страница 3: ...120 t Cycle time 2 125 2 for SSR 20 for relay See 4 6 Sn Input type 0 37 0 K type TC See 4 7 dP Decimal point position 0 3 0 See 4 8 P SL Display low limit 1999 9999 C or F 100 P SH Display high limit 1999 9999 C or F 2500 Pb Input offset 1999 4000 1999 9999 C or F 0 0 See 4 10 OP A Output mode 0 2 0 See 4 11 OUTL Output low limit 0 110 0 OUTH Output high limit 0 110 100 AL P Alarm output definiti...

Страница 4: ...At 1 or At 2 4 5 Control action explanations 4 5 1 PID Please note that because this controller uses fuzzy logic enhanced PID control software the definition of the control constants P I and d are different than that of the traditional proportional integral and derivative parameters In most cases the fuzzy logic enhanced PID control is very adaptive and may work well without changing the initial P...

Страница 5: ...imum ALM1 Hy 1 and Hy 2 to 9999 ALM2 to 1999 to stop its function 4 14 COOL for Celsius Fahrenheit Heating and Cooling Selection Parameter COOL is used to set the display unit heating or cooling and alarm suppression Its value is determined by the following formula COOL AX1 BX2 CX8 A 0 reverse action control mode for heating control 4 5 3 Manual mode Manual mode allows the user to control the outp...

Страница 6: ...cy within a fraction of a degree The SSR allows the heater to be switched at higher frequency for better stability It also has longer life time than the electromechanical relay A proper heat sink is needed when the SSR switches 8A of current For wiring a 240V heater please see 5 4 A 1 direct action control mode for cooling control B 0 without alarm suppressing when turned on or when set point chan...

Страница 7: ...esis band for heater and cooler to 2 degree 2 COOL 9 Set the controller to cooling mode no alarm suppression Fahrenheit temperature unit display 3 AT 0 Set the controller main output to on off control mode for refrigerator compressor control 4 ALM2 62 Set the low limit alarm to 62 F Heater will be on at 60 F ALM2 Hy and off at 64 F ALM2 Hy 5 SV 67 Refrigerator will be on at 69 F SV Hy and off at 6...

Страница 8: ...e parameter OUTL If this happens when using thermocouple sensor you can short terminal 4 and 5 with a copper wire If the display shows ambient temperature the thermocouple is defective If it still displays orAL check the input setting Sn to make sure it is set to the right thermocouple type If the Sn setting is correct the controller is defective For RTD sensors check the input setting first becau...

Отзывы: