background image

Depending on the amount of water in the cooker, the performance may vary slightly. If 
the temperature still overshoots too much, increase the P value. If the temperature 
stabilizes one degree below the set point, reduce the P value. 
 

Technical explanation 

For people used to a conventional thermocouple or RTD sensor based PID controller, 
they may think a PD controller can’t hold the temperature within one degree, because a 
few degree temperature offset is needed for the controller to output enough power to 
maintain stability. However, this is not true for a thermistor sensor based controller, 
because a thermistor sensor is much more sensitive. A 0.3 degree offset is sufficient for 
the controller sending enough power to maintain the temperature within one degree of 
set point. 
 

B) Proportional, Integral and Derivative (PID) mode.

   

The advantage of using the PID mode is fast action and no temperature offset (<1 
degree) in long duration cooking. The disadvantage of PID mode is that there will be a 
small temperature overshoot. Depending on the parameters used, the temperature may 
oscillate several times before it settles to the set temperature. Because the very slow 
response of the slow cooker, it is very difficult to not have any temperature overshoot 
when PID mode is used. However, if you are making sous-vide and want to drop the food 
pouches into the pot after temperature is close to the set point, this small temperature 
overshoot actually will help the cooking and is preferred by many cooks. This is because 
in most cases, the overshoot is not high enough and long enough to bring the food 
temperature above the set point. It will help to bring the food temperature reach desired 
temperature faster. 
The following parameters worked well for our test. 

 

Symbol P 

C-F 

Display 

P I  d C-F 

Slow cooker, 4 quart 

54

60

15 

°F 

Slow cooker, 4 quart 

30

60

15 

°C 

Slow cooker, 7 quart 

180

700

40 

°F 

Slow cooker, 7 quart 

100

700

40 

°C 

It should be noted that these parameters are not optimized if the amount of water in the 
pot is different. In general, weaker parameters (i.e., higher P and I) should be used when 
a larger mass is heated (except that the derivative action should be lower). Larger mass 
has larger heat inertia, so it needs to be moved more slowly to control. For the derivative 
action, strong action will reduce the overshoot. In terms of long term temperature 
precision, the difference in these parameters will have very little effect. 

 
 

18

 

 
 

Содержание WS-1500A

Страница 1: ...pliances and your safety is paramount SAFETY WARNINGS This controller is designed only to be used with devices that have limited power and their own thermal cut off protection such as a thermostat or...

Страница 2: ...es caused by misuse of the controller If you are not sure the controller can be used please contact Auber Instruments before use If an abnormal display or noise is observed turn the controller off unp...

Страница 3: ...Controller Mode PID PI PD or P Output switching device Built in optically isolated solid state relay with zero voltage crossing switching Sensor tip dimensions 5 mm diameter x 70 mm long Sensor cable...

Страница 4: ...erature settings getting into parameters setting mode and confirming various actions taken 4 Key To increment displayed value 5 Key To decrement displayed value 6 Time Key Change the Parameter Window...

Страница 5: ...ollowing steps Plug the temperature sensor to the back of the controller Plug the power cord to the back of the controller and the other end to the power outlet on the wall Turn on the controller to m...

Страница 6: ...onfirmed The display will return to the normal display mode if no key is pressed within 3 seconds Using the timer The timer can be used in two different ways a Use it as timer If you set the timer for...

Страница 7: ...d 2 that it must be tuned to the cooker being used Tuning is the process that matches the control characteristics of the controller to the heating characteristics of the cooker The controller is said...

Страница 8: ...ostat or power control turn both as high as they ll go Set the controller to the appropriate power level see next Section Turn the controller and cooker on and then enter the desired set point tempera...

Страница 9: ...off This constant also affects both integral and derivative action Smaller P values will make the both integral and derivative action stronger Please note the value of the P is temperature unit sensi...

Страница 10: ...show P for a second and then its P setting value Use and keys to change the setting When finished press the SET again to confirm the change The display will show the I for a second and its I setting...

Страница 11: ...the temperature with proper PID parameters it is much easier to control if you limit the maximum output to 25 Ideally an optimized temperature control system should consume about 25 of the heater powe...

Страница 12: ...o confirm the change For example if the temperature is 1 C too high during calibration then use to set the value to 1 to offset value Setting the output reduction The parameter window will first show...

Страница 13: ...days If your appliance fails to operate properly while in use under normal household conditions within the warranty period return the complete appliance and accessories to Auber Instruments 730 Culwor...

Страница 14: ...efore the above may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state or province to province Important Carefully pack it...

Страница 15: ...e about 1 3 watts of heat When 15 Amp is passing through the controller 20 watt of heat is produced in the controller As more heat is produced the temperature inside the controller will rise If it rea...

Страница 16: ...e current is much lower making heat not an issue 2 Limit maximum output power If you set output reduction parameter to 80 then a 15 A heater will become a 12 A heater It will take 25 longer time to he...

Страница 17: ...et Based on the temperature controlling method we can classify the slow cooker control method into two classes PID and PD when I 0 No I We will discuss the advantages and limitations of each method A...

Страница 18: ...s to the set temperature Because the very slow response of the slow cooker it is very difficult to not have any temperature overshoot when PID mode is used However if you are making sous vide and want...

Страница 19: ...ttle will affect the heating speed It will also affect the control quality When the water volume is less than 0 5 liter it might become difficult to control In that case you need to reduce the output...

Отзывы: