Appendix 

 

Technical Talk -- How does it Work? v1.2 

 
There are three commonly used methods for AC power control.  
 
1) 

Phase angle firing

. In this method, the AC power control is achieved by firing the SCR at different phase angle. This is how our SSVR works. This method offer the 

most uniform power output. But the output is very difficult to be adjusted linearly due to the shape of the sine wave. Because of the sharp cut off, there is a potential 
electromagnetic interference (EMI or RFI) if there are inductive devices on the power line. Some of the inductive devices cannot be controlled by this method. 
 

 

Figure 4. SSVR and TRIAC use phase-angle firing to regulate the power. 

 
 

 

Figure 5. Original AC sine wave is overlaid with SSVR output wave form. The blue colored area shows the power output that has been blocked. 

 
 
2) 

Time proportional firing

. A fixed cycle time needs to be defined in this method. Then, the controller or regulator adjusts the on time during each cycle to achieve 

the power control. For example, if the cycle time is 1 second, turn on the power for 0.25 second for every 1 second means a 25% power output. Most of PID controllers 
use this method to control SSRs. This is also how the manual mode of Auber's PID controller works, except the cycle time has to be 2 second or longer. 
Using this method, the user can linearly adjust output. But the power output is pulsed at each cycle. The shortest cycle time for most PID is either 1 or 2 second. 
Therefore, power is pulsed at 1 or 2 seconds. When heating a liquid, heat is not transferred as smooth as the phase-angle fire method. 
 

Содержание EZboil DSPR310D

Страница 1: ...n 2 seconds after you stop the adjustment 4 AL1 indicator This red LED indicates the status of Relay 1 AL1 When it is on relay 1 is closed when it is off relay 1 is open 5 AL2 indicator This red LED indicates the status of Relay 2 AL2 When it is on relay 2 is closed when it is off relay 2 is open 6 Mashing mode indicator MASH This yellow LED light indicates the operation mode of the controller Whe...

Страница 2: ...ep mashing control or boiling control mode Press the knob will set the controller to the operation mode displayed Please check section 5 1 for details Display mode 3 Parameter settings Press down and hold the knob for 5 seconds to enter the display mode 3 Please check section 6 for details 5 Operation 5 1 Operation mode selection This controller offers two operation modes step mashing and boiling ...

Страница 3: ...ashing temperature steps User can selectively turn on or off the relay s at specific steps These relays can also be programmed to be synchronized with the internal beeper so that external buzzer can be used for notification at the beginning and end of each step see section 6 4 2 note 12 5 2 4 Adjusting parameter value Two ways to adjust set temperature 1 To adjust the set temperature in current st...

Страница 4: ...ettings Knob Press Knob Press Rotate Knob Rotate Knob Knob Press goto rely Enter Relay settings Knob Press Rotate Knob goto syst Enter System settings Knob Press Rotate Knob Figure 5 Parameter group selection Tip 1 When timer is started you will hear the beeping notification Please see section 9 in page 10 for details Tip 2 Similar to mashing mode you can even hold the timer by pressing key B mome...

Страница 5: ... alternately In other word the timer for step mashing mode is countdown timer Note 4 Timer Function tSP EO When the program is end please check section 5 2 2 for the difference between end and stop the controller will generate six long beeps The top display will switch between the current temperature and End alternately After timer ends the power output can be configured either to continue heating...

Страница 6: ...to prog Knob C 1 122 Knob T 2 00 20 Knob C 8 50 Knob 80 100 Knob T 8 00 00 Step 1 set temp Step 2 time duration Step 8 set temp End Press Press Press Press Press T 1 00 30 Knob C 2 140 Knob Step 1 time duration Step 2 set temp Press Press Step 8 time duration Figure 8 Flow chart of setting step program settings 6 3 Boiling Parameters Parameters the configure the boiling control are grouped under t...

Страница 7: ...2 and the buzzer will go off when the second even starts Event timer botX i e bot1 bot2 bot3 botX the time duration of each event where X is the event number 1 9 X is decided by parameter nE Time duration of an event botX is the boiling time of an ingredient to be added to the boiling wort bot1 is the first event timer which starts from the moment that the first ingredient is added until the end o...

Страница 8: ...N this relay can be programmed to be activated at target boiling step or steps Parameter rLP is used for programming see below Beep In this mode relay is synchronized with internal buzzer When the built in buzzer beeps this relay also turns on This will allow the user to drive an external flashing buzzer for louder and visual notification ALbE Alarm and beep mode Take relay 1 as an example relay 2...

Страница 9: ...re determined period of time User can set the pulse duration by the AP parameter in the menu of alarm settings it ranges from 1 to 100 seconds This feature is useful in situations where a user only need to ring the buzzer for a short time or want to drive an external load for a fixed amount of time duration When LAt it is set to N Non Latching rL ALM ALbE only the relay action will follow the alar...

Страница 10: ...g diagrams of how to connect a DC triggered AC SSR with this power regulator SSR 1 2 3 13 14 6 7 8 9 10 4 5 RTD R R W 120V AC L N Heater 3 4 SSR 3 4 1 2 3 13 14 6 7 8 9 10 4 5 RTD R R W Heater 240V AC L1 L2 Figure 13 Wiring examples of controlling a heater with SSR and DSPR310D in a 120VAC system upper and in a 240VAC system lower Example 2 Here is the wiring diagram of how to wire two external bu...

Страница 11: ...essage or incorrect temperature reading if your sensor is not connected or your sensor is bad Top display will flash orAL and 932 alternately if you set it to Fahrenheit display C F F or orAL and 500 alternately if you set it to Celsius display C F C Auber Instruments 5755 North Point Parkway Suite 99 Alpharetta GA 30022 www auberins com Email info auberins com Tel 770 569 8420 Copyright 2007 2018...

Страница 12: ...ower Figure 5 Original AC sine wave is overlaid with SSVR output wave form The blue colored area shows the power output that has been blocked 2 Time proportional firing A fixed cycle time needs to be defined in this method Then the controller or regulator adjusts the on time during each cycle to achieve the power control For example if the cycle time is 1 second turn on the power for 0 25 second f...

Страница 13: ...al drop to zero the AC power is blocked 3 Burst firing This method is similar to time proportional firing section 2 But in contrast to the time proportional mode where the SSR is fired once for each fixed cycle period which are usually 2 seconds or longer the regulator will find the minimum cycle time to achieve the desired output percentage The on pulse can be as short as one AC cycle So power is...

Страница 14: ... DSPR detects the frequency and phase of the AC power line so that the pulse width and firing time is synchronized with AC cycle Auber Instruments 5755 North Point Parkway Suite 99 Alpharetta GA 30022 www auberins com Email info auberins com Tel 770 569 8420 Copyright 2007 2018 Auber Instruments All Rights Reserved No part of this manual shall be copied reproduced or transmitted in any way without...