background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2018.08                                                                    

   

                                                              P9/14 

 

Note for mashing mode:

 If you set to turn on the relay at step 1 only, relay will 

be activated when you start the whole program (when you press key A), and 
will be deactivated when step 1 is finished. 

It doesn’t affect if the timer 

in step 

mashing mode has not been started yet. If you set to turn on the relay at other 
step, relay will be activated from the moment when the previous step is 
finished, to the moment when the current step is finished. If you set to turn on 
the relay at continuous steps (for example, step 2 and 3), the relay will remain 
at ON position during the transition period(s) between steps.  
 
For example, if you set relay 1 is synchronized with mashing steps (LP1 = M-
SN), and if you set to turn on relay 1 at step 1 & 2 only (rLP1 = 3), once you 
press the key A to start the program, relay 1 will be turned ON immediately 
(even the step timer has not been started yet). Relay 1 will remain at ON 
position during the transition period between step 1 and step 2 (where there 
might be a timer gap/acceleration period). When the controller has finished 
step 2, relay 1 will be OFF immediately (you will hear the four 2s long beeping 
to alert you the current step is finished). In other word, the relay 1 will be turned 
on from the moment when you press key A to start the whole program, to the 
moment when step 2 has been finished.    

Note for boiling mode:

 The definition for timer event here (for rLP calculation) 

is different than the timer event in boiling mode (section 6.3). The timer event 
here is the interval time from the beginning of current timer event to the 
beginning of next timer event (like mashing mode). 

Current event doesn’t 

include the time of next event.   
 
Example: If the first ingredient (bot1) needs 60 minutes, the second ingredient 
(bot2) needs 10 minutes and third ingredient (bot3) needs 1 minutes of boil, you 
set Bot1 = 1:00, Bot2 = 00:10, Bot3 = 00:01. The event 1 for relay is the time 
from 00:00 to 00:50 (if counting up) or 1:00 to 00:10 (if counting down). Event 2 
for relay is the time from 00:50 to 00:59 (if counting up) or 00:10 to 00:01 (if 
counting down). Event 3 for relay is the time from 00:59 to 01:00 (if counting up) 
or 00:01 to 00:00 (if counting down). If you set relay 2 for B-SN, and if you set 
rLP2 to 2, relay 2 will be activated during event 2 for relay only, which is the time 
from 00:50 to 00:59 (if counting up) or 00:10 to 00:01 (if counting down). 
 

Calculation Example:  

a) To turn on relay 1 on step/event 2 and step/event 3 only, rLP1 needs to be 
set to 6: 
 

rLP1 = 0*1 + 1*2 + 1*4 + 0*8 + 0*16 + 0*32 + 0*64 + 0*128 + 0*256 = 6 

 
b) To turn on relay 2 from step/event 1 to step/event 5, rLP2 needs to be set to 
31: 
 

rLP2 = 1*1 + 1*2 + 1*4 + 1*8 + 1*16 + 0*32 + 0*64 + 0*128 + 0*256 = 31 

 

Note 14: Settings for Process Alarm (rL = ALM or ALbE)

 

The following parameters are only applicable if this relay is set to process 
alarm (rL = ALM or ALbE): LAt, SiL, AH, AL, HY and AP2 

 

Note  14.1:  LAt 

(Relay  Action,

  rL  =  ALM/ALbE  only

)

,

  determines  the  relay 

actions when alarm conditions are met and/or then removed. It can be set to

 

PUL

 for pulsing mode, or 

N

 for Normal Mode. 

 
When 

LAt

 is set to 

PUL

 (Pulsing Mode,

 rL = ALM/ALbE only

), the replay action 

is a timed single pulse. When the alarm condition is met, relay will be activated 
only for a pre-determined period of time. User can set the pulse duration by the 

AP

 parameter in the menu of alarm settings; it ranges from 1 to 100 seconds. 

This feature is useful in situations where a user only need to ring the buzzer for 
a short time or want to drive an external load for a fixed amount of time duration.  
 
When 

LAt

 it is set to 

N

 (Non-Latching,

 rL = ALM/ALbE only

), the relay action 

will follow the alarm condition. The relay stops its action when the alarm condition 
is removed. 
 

Note 14.2: SiL (

Relay Silence, also called Alarm Suppression,

 rL = ALM/ALbE 

only)

,  

SiL determines whether a relay action should be suppressed when controller is 
just  powered  up.  Relay  Silence/Alarm  Suppression  is  only  supposed  to  work 
when: 1) absolute low alarm is enabled and 2) the reading temperature is never 
over (AL + Hy) after power up. If the reading temperature has been over (AL + 
Hy), once the reading temperature drops below AL, the alarm will be ON and 
alarm suppression will be disabled.  
 
This feature is useful for the following situation: when a relay is set as low limit 

alarm,  and  you  don’t  want  the  relay  to  pull  in  when  you  just  power  up  the 

controller as the start-up temperature will be in the alarm zone.  
  

Note  14.3:  AH  (

High  Alarm,

  rL  =  ALM/ALbE  only), 

determines  at  what 

temperature  that  is  higher  than  the  set  temperature  the  alarm  relay  will  be 
activated. This setting applies to both process and derivation alarms. The unit is 
in degree C or F. 

AH1

 is for Relay 1 and 

AH2

 for Relay 2. It can be set to any 

temperature that the controller is capable to reading, or set to “

off

”. 

The value of 

AH

 represents the absolute high alarm. The relay will be activated when PV > 

AH, and deactivated when PV < (AH - HY).  
 

Note  14.4:  AL  (

Low  Alarm,

  rL  =  ALM/ALbE  only),

  determines  at  what 

temperature  that  is  lower  than  the  set  temperature  the  alarm  relay  will  be 
activated. This setting applies to both process and derivation alarms. The unit is 
in degree C or F. It can be set to any temperature that the controller is capable 

of reading, or set to “

off

”.

 The value of AL represents the absolute low alarm. 

The relay will be activated when PV < AL, and deactivated when PV > (AL + HY). 
 
Tip 1:  

AL

 should always be less than 

AH

 (AL1 < AH1, AL2 < AH2), otherwise, 

the alarm relay will stay activated all the time.  
Tip 2: A relay can be set to work for process high alarm only (i.e., set 

AL

 = 

off

), 

for process low alarm only (i.e., set 

AH

 = 

off

), or for both high and low alarm.  

 

Note  14.5:  HY  (

Hysteresis  Band,

  rL  =  ALM/ALbE  only),

  determines  the 

hysteresis band between temperature of activating and deactivating alarms. It is 
also called differential band by some manufacturer. The unit is degree F or C. 
For example, Relay 1 is set as a non-latching process alarm with relays settings 

RL1

  = 

ALM

Lgc1

  = 

RL_C

LAt1

  = 

N

AH1

  =  200, 

AL1

  =  100  and 

HY

  =  3 

(temperature unit is F). For the high limit alarm, when the process temperature 

is  greater  and  equal  to  200˚F,  the  relay  will  pull  in;  an

d  when  process 

temperature drops off below 

197˚F, relay will drop off. For the low limit alarm, 

relay will pull in when process temperature is less than 100˚F; and the relay will 
drop off when process temperature is greater to 103˚F. 

 

Relay on

Relay on

PV

PV

Absolute high alarm

Absolute low alarm

SV

AH - Hy

AH

AL

AL + Hy

SV

 

Figure 12. Relationship between Hy and high/low absolute alarm  

 

Note  14.6:  AP  (

Alarm  Pulse,

  rL  =  ALM/ALbE  only),

  determines  the  time 

duration of which a relay stays activated. The unit is second. Pulse length can 
be set from 1 to 100 seconds. 
 

Содержание EZboil DSPR310D

Страница 1: ...n 2 seconds after you stop the adjustment 4 AL1 indicator This red LED indicates the status of Relay 1 AL1 When it is on relay 1 is closed when it is off relay 1 is open 5 AL2 indicator This red LED indicates the status of Relay 2 AL2 When it is on relay 2 is closed when it is off relay 2 is open 6 Mashing mode indicator MASH This yellow LED light indicates the operation mode of the controller Whe...

Страница 2: ...ep mashing control or boiling control mode Press the knob will set the controller to the operation mode displayed Please check section 5 1 for details Display mode 3 Parameter settings Press down and hold the knob for 5 seconds to enter the display mode 3 Please check section 6 for details 5 Operation 5 1 Operation mode selection This controller offers two operation modes step mashing and boiling ...

Страница 3: ...ashing temperature steps User can selectively turn on or off the relay s at specific steps These relays can also be programmed to be synchronized with the internal beeper so that external buzzer can be used for notification at the beginning and end of each step see section 6 4 2 note 12 5 2 4 Adjusting parameter value Two ways to adjust set temperature 1 To adjust the set temperature in current st...

Страница 4: ...ettings Knob Press Knob Press Rotate Knob Rotate Knob Knob Press goto rely Enter Relay settings Knob Press Rotate Knob goto syst Enter System settings Knob Press Rotate Knob Figure 5 Parameter group selection Tip 1 When timer is started you will hear the beeping notification Please see section 9 in page 10 for details Tip 2 Similar to mashing mode you can even hold the timer by pressing key B mome...

Страница 5: ... alternately In other word the timer for step mashing mode is countdown timer Note 4 Timer Function tSP EO When the program is end please check section 5 2 2 for the difference between end and stop the controller will generate six long beeps The top display will switch between the current temperature and End alternately After timer ends the power output can be configured either to continue heating...

Страница 6: ...to prog Knob C 1 122 Knob T 2 00 20 Knob C 8 50 Knob 80 100 Knob T 8 00 00 Step 1 set temp Step 2 time duration Step 8 set temp End Press Press Press Press Press T 1 00 30 Knob C 2 140 Knob Step 1 time duration Step 2 set temp Press Press Step 8 time duration Figure 8 Flow chart of setting step program settings 6 3 Boiling Parameters Parameters the configure the boiling control are grouped under t...

Страница 7: ...2 and the buzzer will go off when the second even starts Event timer botX i e bot1 bot2 bot3 botX the time duration of each event where X is the event number 1 9 X is decided by parameter nE Time duration of an event botX is the boiling time of an ingredient to be added to the boiling wort bot1 is the first event timer which starts from the moment that the first ingredient is added until the end o...

Страница 8: ...N this relay can be programmed to be activated at target boiling step or steps Parameter rLP is used for programming see below Beep In this mode relay is synchronized with internal buzzer When the built in buzzer beeps this relay also turns on This will allow the user to drive an external flashing buzzer for louder and visual notification ALbE Alarm and beep mode Take relay 1 as an example relay 2...

Страница 9: ...re determined period of time User can set the pulse duration by the AP parameter in the menu of alarm settings it ranges from 1 to 100 seconds This feature is useful in situations where a user only need to ring the buzzer for a short time or want to drive an external load for a fixed amount of time duration When LAt it is set to N Non Latching rL ALM ALbE only the relay action will follow the alar...

Страница 10: ...g diagrams of how to connect a DC triggered AC SSR with this power regulator SSR 1 2 3 13 14 6 7 8 9 10 4 5 RTD R R W 120V AC L N Heater 3 4 SSR 3 4 1 2 3 13 14 6 7 8 9 10 4 5 RTD R R W Heater 240V AC L1 L2 Figure 13 Wiring examples of controlling a heater with SSR and DSPR310D in a 120VAC system upper and in a 240VAC system lower Example 2 Here is the wiring diagram of how to wire two external bu...

Страница 11: ...essage or incorrect temperature reading if your sensor is not connected or your sensor is bad Top display will flash orAL and 932 alternately if you set it to Fahrenheit display C F F or orAL and 500 alternately if you set it to Celsius display C F C Auber Instruments 5755 North Point Parkway Suite 99 Alpharetta GA 30022 www auberins com Email info auberins com Tel 770 569 8420 Copyright 2007 2018...

Страница 12: ...ower Figure 5 Original AC sine wave is overlaid with SSVR output wave form The blue colored area shows the power output that has been blocked 2 Time proportional firing A fixed cycle time needs to be defined in this method Then the controller or regulator adjusts the on time during each cycle to achieve the power control For example if the cycle time is 1 second turn on the power for 0 25 second f...

Страница 13: ...al drop to zero the AC power is blocked 3 Burst firing This method is similar to time proportional firing section 2 But in contrast to the time proportional mode where the SSR is fired once for each fixed cycle period which are usually 2 seconds or longer the regulator will find the minimum cycle time to achieve the desired output percentage The on pulse can be as short as one AC cycle So power is...

Страница 14: ... DSPR detects the frequency and phase of the AC power line so that the pulse width and firing time is synchronized with AC cycle Auber Instruments 5755 North Point Parkway Suite 99 Alpharetta GA 30022 www auberins com Email info auberins com Tel 770 569 8420 Copyright 2007 2018 Auber Instruments All Rights Reserved No part of this manual shall be copied reproduced or transmitted in any way without...

Отзывы: