Atwood hydro flame 7900-II series Скачать руководство пользователя страница 4

 

 
 

 

 

 

 

 
1. 

Inspect  furnace  installation  and  vent  termination  to  be  sure 
furnace  is  properly  secured  in  place,  that  vent  terminates  to  the 
atmosphere, and that vent tubes overlap properly and vent is tight 
against outer door screen. (See installation manual supplied with 
furnace).  All  exhaust  system tubes must  overlap  no  less  than  1-
1/4”.  All  air  intake  tubes  must  overlap  no  less  than  1/2”  and  be 
positioned for proper function. 

2. 

Inspect  chamber  and  venting  to  assure  that  these  components 
are  physically  sound,  without  holes  or  excessive  corrosion  and 
that  the  installation  and/or  reinstallation  are  in  accordance  with 
Atwood  Mobile

 

Products  Installation  Instructions.  (Reference 

Installation Manual supplied with furnace.) 

3. 

Check  the  base  on  which  furnace  is  mounted.  Be  sure  it  is 
physically sound, void of any sagging, deterioration, etc. 

4. 

Inspect furnace, the venting, ducting and the gas piping to furnace 
for  obvious  signs  of  deterioration.  Correct  any  defects  at  once. 
Always verify proper operation of furnace after servicing. 

5. 

Do  not  allow  flue  gas  exhaust  to  have  extended  contact  with 
exterior sidewall of recreation vehicle. It will cause the material to 
degrade over time. 

6. 

You,  as  the  owner/user,  should  inspect  the  furnace  monthly 
during the heating season for presence of soot on vent. Operating 
the  furnace  under  this  condition  could  lead  to  serious  property 
damage, personal injury or loss of life. If soot is observed on the 
vent,  immediately  shut  furnace  down  and  contact  a  qualified 
service agency. 
 

 

GAS CONVERSION 
 

All  models,  except  the  8900  AC  Series,  are  designed  for  LP  GAS 
ONLY and cannot be converted to natural gas. To verify the setting of 
your furnace, open furnace door and check the model number on the 
label,  (see  table  below).  Use  only  the  type  of  gas  your  furnace  has 
been set for.  
 
Model 

Gas Type 

Model 

Gas Type 

All 7900 

LP ONLY 

8900 DC 

LP ONLY 

All 8012 

LP ONLY 

8900 AC (LC) 

LP or NAT 

All 8500 

LP ONLY 

LC = LP Convertible Unit  

 

 

AC model units come equipped with a convertible gas control.  

 

Each unit is supplied with two main burner orifices. One will be in 
place; the other will be attached to the blower housing cover.  

 

Each orifice will be clearly marked with a drill size as shown 
below. 

 

The pressure settings of the convertible valve are set for natural 
gas NAT 3.5” WC or LP 10.5” WC and are not adjustable.  

 

Use Loctite* #RC609 or some other thread lock sealant on orifice 
threads when installing a new orifice. 

 

A 1/8” NPT plug is provided upstream of gas connections for 
checking gas pressure. 

 

GAS 

TYPE 

BTU/HR 

LINE 

PRESSURE 

REG. PLUG 

SETTING 

DRILL 

SIZE 

Propane 

(LP) 

40,000 

11” WC 

10.5” WC 

49P 

Natural 

(Nat) 

40,000 

7” WC 

3.5” WC 

30N 

Propane 

(LP) 

35,000 

11” WC 

10.5 WC 

51P 

Natural 

(Nat) 

35,000 

7” WC 

3.5” WC 

32N 

*WC= Water Column 
 

VALVE CONVERSION 

 

 
1. 

See drawing to check exposed section on side of adjustment reg. 
plug to determine whether it is set for natural or propane. NAT 
stamped on one end and LP stamped on the other end of plug. 
The types of gas in use will be showing right side up when 
installed. 

2. 

Unscrew plug and remove from valve reg. tower. DO NOT 
remove rod from inside the reg. tower or make any adjustments. 
A. 

When set for LP and NAT is required: Unscrew plug and 
replace plug into tower with NAT in up position. NAT should 
now be visible. Finger tighten plug or with small wrench. 
DON’T over tighten. 

B. 

When set for NAT and LP is required: Unscrew plug and 
replace plug into tower with LP in up position. LP should now 
be visible. Finger tighten plug or with small wrench.  DON’T 
over tighten. 

3. 

This plug has been factory calibrated for this valve only.  DO NOT 
modify and DO NOT use plug on any other valve. 

4. 

Install the correct main burner orifice per the chart. 

 

ORIFICE REPLACEMENT 
 

1. 

Remove rain shield by removing one screw from combustion 
cover and tilting rain shield 45° to the right and removing. 

2. 

Remove burner assembly by removing three screws from back 
wall of control box. 

3. 

Remove two screws holding the burner to the manifold. 

4. 

Unscrew the orifice with a 7/16” wrench or socket and replace 
with the correct orifice per the chart corresponding to type of gas 
required, which corresponds to the regulator plug setting. 

5. 

Replace two screws holding burner to manifold. 

6. 

Reinstall the burner assembly and put the three screws back into 
the control box wall. 

 WARNING 

FIRE OR EXPLOSION 

 

 

Use the correct gas specified for you furnace. 

 

Only a qualified Service Technician may convert an 
8900 series furnace from LP to NAT or NAT to LP. 

  

WARNING 

CARBON MONOXIDE POISONING 

 

 

Doors must be properly sealed and draft cap and assemblies 
must  be  adjusted  and  sealed  correctly  to  prevent  carbon 
monoxide from entering coach. 

 

Combustion  air  must  NOT  be  drawn  from  within  any  living 
area. 

 

DO  NOT  vent  exhaust  into  living  area  or  outside  into  an 
enclosed porch area. 

 

DO  NOT  vent  any  other  appliance  with  venting  systems 
serving the furnace. 

 

DO NOT allow snow or any objects to block exhaust system 
of furnace. 

  

WARNING 

POSSIBLE INJURY OR DEATH 

 

It is imperative that the products of combustion be properly vented 
to  atmosphere  and  that  all  combustion  air  supplied  to  burner  is 
drawn from outside atmosphere. 

Содержание hydro flame 7900-II series

Страница 1: ...ation service or maintenance can cause property damage personal injury or loss of life Refer to the installation instructions and or owners manual provided with this appliance CAUTION PERSONAL INJURY DO NOT touch exterior exhaust grills when furnace is operating Supervise young children in the same room as the furnace WARNING POSSIBLE INJURY OR DEATH Your furnace should be inspected by a qualified...

Страница 2: ...r use gasoline or other flammable vapors and or liquids in the vicinity of this or any other appliance DO NOT use the furnace cabinet area as a storage compartment DO NOT block furnace outlet registers or return air grills Keep all insulating material away from furnaces HOW TO TURN OFF ELECTRICAL POWER 1 Set the thermostat at the lowest setting 2 Open furnace exterior door and turn OFF electrical ...

Страница 3: ... products of combustion being vented into the room or occupied areas In any installation in which the vent of the appliance can be covered due to the construction of the RV or some special feature of the RV such as slide out pop up etc Always insure that the appliance cannot be operated by setting the thermostat to the positive OFF position and shutting off all electrical and gas supply to the app...

Страница 4: ...upstream of gas connections for checking gas pressure GAS TYPE BTU HR LINE PRESSURE REG PLUG SETTING DRILL SIZE Propane LP 40 000 11 WC 10 5 WC 49P Natural Nat 40 000 7 WC 3 5 WC 30N Propane LP 35 000 11 WC 10 5 WC 51P Natural Nat 35 000 7 WC 3 5 WC 32N WC Water Column VALVE CONVERSION 1 See drawing to check exposed section on side of adjustment reg plug to determine whether it is set for natural ...

Страница 5: ...he discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or other cause not arising from defects in material workmanship This warranty extends to the original owner of the product only and is subject to the following conditions 1 For two years from the date of purchase Atwood will repair or replace any part defective in ...

Страница 6: ...or warranty service rendered on a direct basis only 4 Repairs replacement parts and or furnace replacement authorized by Atwood shall be subject to the remainder of the warranty of any of the aforesaid two year period EXCLUSIONS SPECIFICALLY EXCLUDED FROM THE WARRANTIES 1 Incidental or consequential damages 2 Damage caused by shipment 3 Damage resulting from improper installation misuse neglect ac...

Страница 7: ...7 EXTENDED SERVICE ORDER FORM ...

Страница 8: ...THIS PAGE INTENTIONALLY LEFT BLANK CETTE PAGE EST INTENTIONNELLEMENT VIDE ...

Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK CETTE PAGE EST INTENTIONNELLEMENT VIDE ...

Страница 10: ...THIS PAGE INTENTIONALLY LEFT BLANK CETTE PAGE EST INTENTIONNELLEMENT VIDE ...

Страница 11: ... service qualifié pour inspecter l appareil et remplacer toute pièce du système de commande et toute commande de gaz qui a été en contact avec de l eau AVERTISSEMENT INCENDIE OU EXPLOSION Assurez vous que la fournaise et tous les systèmes d allumage sont sur OFF ARRÊT durant tout processus de ravitaillement en carburant et pendant que le véhicule est en mouvement ou est remorqué AVERTISSEMENT BLES...

Страница 12: ...PAS ou n utilisez pas de l essence ou tout autre liquide ou vapeur inflammable à proximité de cette fournaise ou tout autre appareil N UTILISEZ PAS la zone de l armoire de la fournaise comme compartiment d entreposage NE BLOQUEZ PAS les registres de sortie de la fournaise ou les grilles d air repris Gardez tout le matériel d isolation loin des fournaises COMMENT COUPER LE COURANT ÉLECTRIQUE 1 Régl...

Страница 13: ... attention à la ventilation de votre fournaise Pour votre sécurité ne raccordez pas l évent de la fournaise à l intérieur de pièces ajoutées du grillage de la véranda ou sur les terrasses Ceci entraînerait la ventilation des produits de combustion à l intérieur de la pièce ou les aires habitables Dans toute installation dans laquelle l évent de l appareil peut être couvert en raison de la construc...

Страница 14: ...f frein filet sur les fils d orifice lors de l installation d un nouvel orifice Une prise NPT de 1 8 est fournie en amont des connexions de gaz pour vérifier la pression de gaz TYPE DE GAZ BTU HR PRESSION DE LIGNE RÉGLAGE DU BOUCHON REG GRANDEUR DE FORET Propane LP 40 000 11 WC 10 5 CE 49P Naturel Nat 40 000 7 WC 3 5 CE 30N Propane LP 35 000 11 WC 10 5 CE 51P Naturel Nat 35 000 7 WC 3 5 CE 32N CE ...

Страница 15: ... ou usées GARANTIE Atwood Mobile Products GARANTIE LIMITÉE DE LA FOURNAISE hydro flammeMC Atwood Mobile Products garantit au propriétaire original et sous réserve des conditions mentionnées ci dessous que le produit hydro flammeMC sera exempt de défauts de fabrication et de matériau pendant une période de deux ans suivant la date d achat originale La responsabilité d Atwood en vertu de la présente...

Страница 16: ...rvice de garantie rendu sur une base directe seulement 4 Les réparations les pièces de rechange et ou le remplacement de la fournaise autorisé par Atwood seront assujettis à la période restante de la garantie de toute période de deux ans susvisée EXCLUSIONS SONT SPÉCIFIQUEMENT EXCLUS DES GARANTIES 1 Les dommages indirects ou consécutifs 2 Les dommages causés par une expédition 3 Les dommages surve...

Отзывы: