Regular checks
The following checks should be carried out regularly to ensure safe operation and long service life.
Depending on the environmental and working conditions of the compressor, the local Atlas Copco Service
center may overrule the standard maintenance schedule; always check if in doubt.
Please keep following checks in mind:
• Keep the dryer clean. (if applicable)
• Regularly brush and blow off the finned surface of the air cooler(s) (if applicable)
• Regularly test the water drains
Period
Running hours
Operation
--
At initial start
Check the dryer adjustment as specified in
Initial start-up
.
Daily
8
Check the Elektronikon display for warnings.
Daily
8
Check that condensate is discharged from the drain receivers
during loading.
Daily
--
Before stopping:
• Drain the aftercooler drain receiver
• Drain the intercooler drain receiver
• On Full-Feature compressors, drain the drain receivers of
the internal dryer, and additional aftercooler for energy
recovery units.
Weekly
--
Check the oil level. Refer to
Before starting
.
Weekly
--
Drain condensate from the air receiver, if installed.
Weekly
--
Check for leaks. Tighten leaking connections and replace
damaged/leaking parts.
3-monthly
--
Clean compressor.
3-monthly
500
Check coolers, clean if necessary.
2-yearly
16000
Replace the demister sponge of the integrated dryer.
2-yearly
16000
Inspect the dryer heater
2-yearly
16000
Inspect the dryer rotor
When displayed
--
Carry out service actions according to the displayed service
warnings or service plans as shown below.
• When operating in a dusty atmosphere, inspect the air filters more frequently. Always
use Atlas Copco filters to guarantee the performance of your compressor.
• Grease the motor bearings at the correct interval and with the correct grease type and
quantity as mentioned on the motor data plate. If in doubt, consult your Atlas Copco
Service center.
Service plan
A number of service operations are grouped (called level A, level B, level C, ...). Each level stands for a
number of service actions to be carried out at the time intervals programmed in the Elektronikon regulator.
When a level is reached, a message will appear on the screen. After carrying out all service actions, reset
the interval timers using the "Reset" key in the "Service" menu.
Instruction book
2920 1815 04
283
Содержание ZR 110
Страница 2: ......
Страница 177: ...Dimension drawing of ZR 110 up to ZR 145 Full Feature page 1 Instruction book 2920 1815 04 175 ...
Страница 178: ...Dimension drawing of ZR 110 up to ZR 145 Full Feature page 2 Instruction book 176 2920 1815 04 ...
Страница 179: ...Dimension drawing of ZT 110 up to ZT 145 page 1 Instruction book 2920 1815 04 177 ...
Страница 193: ...Drawings DIN to JIS adaptor flange with inner pipe diameter ranging from 32 to 65 mm Instruction book 2920 1815 04 191 ...
Страница 194: ...DIN to JIS adaptor flange with inner pipe diameter ranging from 80 to 125 mm Instruction book 192 2920 1815 04 ...
Страница 204: ...Installation proposal for ZT 110 up to ZT 145 and ZT 132 160 VSD Instruction book 202 2920 1815 04 ...
Страница 214: ... CORRECT installation Instruction book 212 2920 1815 04 ...
Страница 230: ...Electric connections for compressors with star delta starter Model year 2014 Instruction book 228 2920 1815 04 ...
Страница 231: ...Electric connections for compressors without a starter Model year 2003 Instruction book 2920 1815 04 229 ...
Страница 248: ...Start up Electric cabinet of compressor with starter Model year 2003 Instruction book 246 2920 1815 04 ...
Страница 249: ...Electric cabinet of compressor with starter Model year 2014 Instruction book 2920 1815 04 247 ...
Страница 250: ...Electric cabinet of compressor without starter Model year 2003 Instruction book 248 2920 1815 04 ...
Страница 257: ...Regulation valves for ZR Full Feature compressors without dryer by pass Instruction book 2920 1815 04 255 ...
Страница 258: ...Regulation valves for ZR Full Feature compressors with dryer by pass Instruction book 256 2920 1815 04 ...
Страница 259: ...Regulation valves for ZR Full Feature compressors without dryer by pass Instruction book 2920 1815 04 257 ...
Страница 260: ...Regulation valves for ZR Full Feature compressors with dryer by pass Instruction book 258 2920 1815 04 ...
Страница 261: ...Regulation valves for ZT Full Feature compressors without dryer by pass Instruction book 2920 1815 04 259 ...
Страница 266: ...Drain connections on ZR 160 Full Feature up to ZR 275 Full Feature Instruction book 264 2920 1815 04 ...
Страница 269: ...Control panel Control panel of Elektronikon GraphicPlus controller Instruction book 2920 1815 04 267 ...
Страница 289: ...10 2 Oil and oil filter change Oil system Oil system components ZR 110 up to ZR 275 Instruction book 2920 1815 04 287 ...
Страница 326: ......
Страница 327: ......