![Atlas Copco ZR 110 Скачать руководство пользователя страница 224](http://html.mh-extra.com/html/atlas-copco/zr-110/zr-110_instruction-book_3001728224.webp)
Compressors designed for a maximum ambient temperature of 122 °F (50 °C) with IE2 motors
Type
Cables (H07V2-K) IEC 60364-5-52:
E & 4
mm
2
Fuses gL/gG
(A)
Maximum cable length
(m)
ZR/ZT 110
2 x (3x 150 + 95)
2X (3X 250)
370
ZR/ZT 145
2 x (3x 150 + 95)
2X (3X 250)
370
ZR/ZT 160
4 x (3x 95 + 50)
2X (3X 315)
207
ZR/ZT 200
4 x (3x 150 + 95)
2X (3X 400)
202
ZR/ZT 250
4 x (3x 150 + 95)
2X (3X 400)
202
Compressors designed for a maximum ambient temperature of 122 °F (50 °C) with IE3 motors or
with oversized motors
Type
FLA
MCA
Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(gL/gG)
Maximum
fuse (A)
(gL/gG)
Icc
ZT/ZR 110
262
289
4 X (3 X 50+25)
181
2 x(3 X 200) 315
50 kA
ZT/ZR 145
262
289
4 X (3 X 50+25)
181
2 x(3 X 200) 315
50 kA
ZT/ZR 160
340
374
4 X (3 X 70+35)
205
2 x(3 X 250) 400
50 kA
ZT/ZR 200
395
434
4 X (3 X 95+50)
205
2 x(3 X 315) 500
50 kA
ZT/ZR 250
495
545
4 X (3 X 150+95)
261
2 x(3 X 400) 500
50 kA
FLA and MCA based on an air-cooled full option compressor.
Icc only achieved with recommended fuses.
460 V - 60 Hz CSA/UL
Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE2 motors
Type
Cables (90° cable) CEC
C22.1
Fuses RK5
(A)
Fuses LPJ
(A)
Maximum cable
length
(m)
ZR/ZT 110
2 x (3x MCM 250 + AWG
3)
2X (3X 175)
2X (3X 600)
193
ZR/ZT 145
4 x (3xAWG 000 + AWG 2) 2X (3X 250)
2X (3X 600)
120
ZR/ZT 160
4 x (3xAWG 000 + AWG 2) 2X (3X 250)
2X (3X 600)
120
ZR/ZT 200
4 x (3xAWG 250 + AWG 0) 2X (3X 300)
2X (3X 600)
184
ZR/ZT 250
4 x (3xAWG 300 + AWG 0) 2X (3X 350)
2X (3X 600)
207
ZR/ZT 275
4 x (3xAWG 300 + AWG 0) 2X (3X 350)
2X (3X 600)
207
Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE3 motors
Type
FLA
MCA
Proposed cable
(mm²)
Maximum
cable
length (m)
Proposed
fuses (A)
(LPJ)
Maximum
fuse (A)
(LPJ)
SCCR
ZT/ZR 110
211
233
2 X (3 X00+4AWG)
180
2 x(3 X
150)
600
65 kA
Instruction book
222
2920 1815 04
Содержание ZR 110
Страница 2: ......
Страница 177: ...Dimension drawing of ZR 110 up to ZR 145 Full Feature page 1 Instruction book 2920 1815 04 175 ...
Страница 178: ...Dimension drawing of ZR 110 up to ZR 145 Full Feature page 2 Instruction book 176 2920 1815 04 ...
Страница 179: ...Dimension drawing of ZT 110 up to ZT 145 page 1 Instruction book 2920 1815 04 177 ...
Страница 193: ...Drawings DIN to JIS adaptor flange with inner pipe diameter ranging from 32 to 65 mm Instruction book 2920 1815 04 191 ...
Страница 194: ...DIN to JIS adaptor flange with inner pipe diameter ranging from 80 to 125 mm Instruction book 192 2920 1815 04 ...
Страница 204: ...Installation proposal for ZT 110 up to ZT 145 and ZT 132 160 VSD Instruction book 202 2920 1815 04 ...
Страница 214: ... CORRECT installation Instruction book 212 2920 1815 04 ...
Страница 230: ...Electric connections for compressors with star delta starter Model year 2014 Instruction book 228 2920 1815 04 ...
Страница 231: ...Electric connections for compressors without a starter Model year 2003 Instruction book 2920 1815 04 229 ...
Страница 248: ...Start up Electric cabinet of compressor with starter Model year 2003 Instruction book 246 2920 1815 04 ...
Страница 249: ...Electric cabinet of compressor with starter Model year 2014 Instruction book 2920 1815 04 247 ...
Страница 250: ...Electric cabinet of compressor without starter Model year 2003 Instruction book 248 2920 1815 04 ...
Страница 257: ...Regulation valves for ZR Full Feature compressors without dryer by pass Instruction book 2920 1815 04 255 ...
Страница 258: ...Regulation valves for ZR Full Feature compressors with dryer by pass Instruction book 256 2920 1815 04 ...
Страница 259: ...Regulation valves for ZR Full Feature compressors without dryer by pass Instruction book 2920 1815 04 257 ...
Страница 260: ...Regulation valves for ZR Full Feature compressors with dryer by pass Instruction book 258 2920 1815 04 ...
Страница 261: ...Regulation valves for ZT Full Feature compressors without dryer by pass Instruction book 2920 1815 04 259 ...
Страница 266: ...Drain connections on ZR 160 Full Feature up to ZR 275 Full Feature Instruction book 264 2920 1815 04 ...
Страница 269: ...Control panel Control panel of Elektronikon GraphicPlus controller Instruction book 2920 1815 04 267 ...
Страница 289: ...10 2 Oil and oil filter change Oil system Oil system components ZR 110 up to ZR 275 Instruction book 2920 1815 04 287 ...
Страница 326: ......
Страница 327: ......