Installation & Servicing instructions ATAG iC-Range
13
8 Mounting boiler frame
Install the boiler in a boiler room in accordance to the actual local regulations BS5440-2:2009.
The installation location of the boiler has to be, and remain, frost-free. The boiler casing is splash water tight
(IPX4D) and is suitable to be installed in e.g. a bathroom.
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is
installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due
to the extremely low surface temperature of the boiler casing during operation. Therefore the requirements of
BS5440:2 may be disregarded.
The boiler can be mounted practically to any wall with the wall frame and the enclosed fixing equipment. The
wall must be flat and of sufficient strength in order to be able to carry the boiler weight with its water content.
Above the boiler there must be at least 210 mm working space in order to be able to fit a horizontal
concentric flue system to the rear (See chapter 9.8 for more flue options). Make sure there is sufficient
service space around the boiler according figure 8.a. The location of the boiler can be determined by using
the template.
The wall frame allows the possibility to pre-fit the complete heating and DHW system before fitting the boiler.
Also the flue system can be prepared. Finally fitting of the flue system is done after fitting the boiler. See next
page for all options for connection the heating, DHW, condensate, flue and gas installation.
Before hanging the boiler to the boiler frame remove the front panel of the boiler first. The front panel is also
the air cabinet and is attached to the boiler case with 2 fasteners (A and B) (see figure 8.a).
Always refit and turn the 2 screws tight in the fasteners A and B.
See chapter 9.8 for further procedure to fit the boiler onto the boiler frame.
Service
dimensions
(in
mm)
Figure
8.a
*Economiser version only
*Economiser version only
100
135*
2.5
2.5
400
Service space
Service space
210
A
B