Installation & Servicing instructions ATAG iC-Range
62
4
Zone 1 parameters
4.0
Set Point
4.0.0
T Day
Room temperature set point for day period
°C
10 ‐ 30
20
4.0.1
T Night
Room temperature set point for night period
°C
10 ‐ 30
15
4.0.2
T set zone 1
Fixed T set for zone 1
°C
Para 4.2.5 to Para 4.2.6
85HT/50LT
( used with Thermoregulation on OFF or Thermoregulation Type 1 )
4.0.3
Zone Frost protection
°C
2 ‐ 15
5
4.1
S/W Changeover
4.1.0
S/W changeover Activation
0 ‐ OFF 1 ‐ ON ( only active when outside temperature influence )
0 ‐ 1
0
4.1.1
Threshold
°C
0 ‐ 30
25
4.1.2
Delay time
time before S/W changeover becomes active
min
0 ‐ 300
300
4.2
Zone 1 settings
4.2.0
Zone 1 system type
0 = low temperature system 1 = high temperature system
0 ‐ 1
1
4.2.1.
Zone 1 thermoregulation type
0 = Fixed flow temperature
0 ‐ 4
0
1 = do not use
2 = Room temperature only
3 = Outdoor Temperature only ( On/Off Thermostat works)
4 = Room + Outdoor temperature ( e‐bus thermostat needed)
4.2.2
Slope Heating Line
0,2 ‐ 1 for Low temperature installations
0,2 ‐ 3,5
0,6 LT / 1,5 HT
1 ‐ 3,5 for high temperature installations
4.2.3
Offset heating line
off set heating line adjustable per °C
°C
‐7 ‐ +7 LT ‐14 ‐ +14 HT
0
Low temperature system ‐7 ‐ +7
High temperature system ‐14 ‐ +14
4.2.4
Room influence proportional
Heating curve proportional Room influence
0 ‐ 20
2 LT ‐ 10 HT
4.2.5
Maximum Temperature
Zone 1 Maximum Flow Temperature
°C
20 ‐ 50LT 20 ‐ 85HT
50 ‐ LT 80 ‐ HT
4.2.6
Minimum Temperature
Zone 1 minimum Flow Temperature
°C
20 ‐ 50LT 20 ‐ 85HT
50 ‐ LT 80 ‐ HT
4.2.8
Quick night set back
do not change
OFF ‐ ON
OFF
4.2.9
Heat Request Mode
do not change
0 ‐ 2
0
4.3
Zone 1 Diagnostics
4.3.4
Heat Request Zone1
is there a Heat demand from this zone 0 ‐ OFF 1 ‐ ON
0‐1
4.7
Zone 1 Regulation parameters
4.7.0
Heating Type
0 = Floor Heating
0 ‐ 5
1
1 = Radiators
2 = Floor heating (main) + Radiators
3 = Radiators (main) + Floor heating
4 = Convection
5 = Air heating
4.7.1
Room influence
0 = OFF
0 ‐ 3
0
1 = Less
2 = Medium
3 = Good
4.7.2
Buiding insulation level
0 = Poor
0‐ 2
0
1 = Average
2 = Good
4.7.3
Buiding size
0 = Small
0 ‐ 2
0
1 = Average
2 = Large
4.7.4
Climate Zone
Setting as a base for the heatline calculation
‐60 ‐ +50
‐10
4.7.5
Auto slope adaptation
0 = Off 1 ‐ On
0 ‐ 1
0
4.7.6
Pre‐heat Function
0 = Off 1 ‐ On
0 ‐ 1
1
5
Settings Zone 2
See zone 1 chapter 4
6
Settings Zone 3
See zone 1 chapter 4
8
Service Parameters
8.0
Boiler statistics‐1
8.0.0
diverter valve
number of divertervalve cycles
times
xx
8.0.1
Pump
number of running hours pump
h
xx
8.0.3
Boiler lifetime
number of hours since 1st boiler power up.
h
xx
8.1
Boiler statistics‐2
8.1.0
Burner on CH
number of hours burner active for CH
h
xx
8.1.1
Burner on DHW
number of hours burner active for DHW
h
xx
8.1.3
Ignition
number of ignition cycles
times
xx
8.2
Boiler
8.2.1
Fan status
Fan: 0 = OFF 1 = ON
8.2.2
Fan speed
Number of revolutions
Rpm
8.2.4
Diverter valve position
position of the diverter valve 0 = DHW 1 = CH
8.2.5
DHW flowrate
l/min
8.2.7
pump modulation
%
8.2.8
gas power
actual boiler power based on fan revolutions
kW
8.2.9
system pressure
bar
8.3
Boiler temperatures
8.3.0
CH T‐Set
calculated target flow temperature
°C
8.3.1
CH flow temperature
°C
8.3.2
CH Return temperature
°C
8.3.3
DHW Temperature
°C
8.3.4
flue gas temperature
only if flue gas sensor is connected
°C
8.3.5
Outside temperature
only if outside sensor is connected or connected to the internet
°C
8.4
Storage
8.4.0
n.a.
8.4.2
n.a.
8.5
Service
8.5.0
Months to next maitenance
Months to go before next Maintenance warning comes up
0‐60
12
8.5.1
Maintenance warning active
switch on or of the maintenance warning 0 = OFF 1 = ON
0 ‐ 1
0
8.5.2
Maintenance warning reset
Reset the maintenance warning in the display and the timer
0 ‐ 1
8.6
Error History
8.6.0
Error history
overview of the last 10 errors occured
8.6.1
Reset Error list
OK = Yes ESC = No
8.7
Free Parameter
8.7.5
Ionization Current
8.7.6
Safety Flame Sensor
burner status of the boiler 0 = OFF 1 = ON
8.7.7
CH Flow switch State
0 = OFF 1 = ON