15.3 Flow restrictor
If required the flow restrictor can be removed as follows:
- Turn off the mains water supply to the boiler
- Open a hot water tap to depressurise the hot water pipe
- Remove the boilers front cover and turn down the control unit
- Remove the securing clip (1) to the front
- Pull out the cap DHW hydroblock (2a) in case of a Combi boiler or;
in case of an Economiser, pull out the IN/OUT flex tube (2b)
- Remove the flow restrictor (3) using a long nose plier
- Refit the cap DHW hydroblock (2a) or IN/OUT flex tube (2b) and secure it with the securing clip (1)
- Turn on mains water inlet and purge water through all taps
- Refit the boilers front cover.
15.4 Component replacement
In the event that parts require replacement, use only genuine parts supplied by ATAG Heating
Technology Ltd.
15.5 User's instructions
Advise the user that for continued efficient and safe operation, the boiler should be serviced at least once a
year by qualified servicing company. It is important and strongly recommended that arrangements are made
for a maintenance agreement with a qualified servicing company to ensure regular servicing of the boiler.
Please contact ATAG Heating Technology Ltd. for further details. Contact details can be found on the back
page of this manual.