700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
15 of 17
17
Troubleshooting Recommendations - con’t
No
Symptom
Recommended Remedy
8
The ADAEZ operator
does not activate when
pushing the INSIDE
pushbutton
·
If RF buttons are used and LED D3 is NOT flashing
perform troubleshooting steps in section “RF transmitters
will not Sync to WIM”
·
If hardwired buttons are used and D3 is NOT flashing:
o
verify wires are connected to the Common (C)
and Normall Open (NO) switch contacts.
o
Use a multimeter to verify a contact closure on
INSIDE BUTTON.
·
IF LED D3 IS flashing & LED D5 IS flashing
o
Verify LEDs on setup board are lighting. If LEDs
on setup board do not light, Erase all learned
codes from the ADAEZ operator and re-sync the
WIM to the operator.
o
Verify ADAEZ operator has been programmed using
the procedure in the Installation and Operating
Instructions.
·
IF LED D3 IS flashing and LED D5 is NOT flashing
o
Verify the jumper on the FIRE PANEL is in place.
·
Turn the Signal Delay switch to the “ON” position.
9
The ADAEZ operator
does not activate when
pushing the OUTSIDE
pushbutton
·
If RF buttons are used and LED D4 is NOT flashing
perform troubleshooting steps in section “RF transmitters
will not Sync to WIM”
·
If hardwired buttons are used and D4 is NOT flashing:
o
verify wires are connected to the Common (C)
and Normall Open (NO) switch contacts.
o
Use a multimeter to verify a contact closure on
INSIDE BUTTON.
·
IF LED D4 IS flashing & LED D5 IS flashing
o
Verify LEDs on setup board are lighting. If LEDs
on setup board do not light, Erase all learned
codes from the ADAEZ operator and re-sync the
WIM to the operator.
o
Verify ADAEZ operator has been programmed
using the procedure in the Installation and
Operating Instructions.
·
IF LED D3 IS flashing and LED D5 is NOT flashing
o
Verify the ACCESS CTR IN contact is closed
while activation is being sent. The WIM will not
accept an OUTSIDE activation unless a valid
access control input is received.
o
Verify OUTSIDE BUTTON DISABLE contact is not
closed.
o
Verify the jumper on the FIRE PANEL is in place.
o
Turn the Signal Delay switch to the “ON” position.