FIREPLACE CLEARANCES (ZC)
Fireplace may be placed directly on a combustible
floor, against a combustible wall at marked
clearances or on a raised wooden platform. If
fireplace is to be installed on a raised wooden
platform, the platform must be a continuous level
surface. The fireplace must be secured in place so it
cannot shift positions. Only header (see below)may
rest on standoffs on top of firebox. When the firebox is
installed over carpeting, vinyl tile, or any combustible
material other than wood flooring, it must be installed
on a metal or wood panel extending its full width
and depth. Alternatively, carpeting, vinyl tile, etc.
may be removed beneath fireplace before installing.
INSTALLING FIREBOX (ZC)
This list of specific instructions will help you make
certain that every installation operation is performed
correctly. Complete installation steps in sequence
shown.
LOCAL BUILDING CODES SHOULD BE CONSULTED
IN ALL CASES AS TO PARTICULAR REQUIREMENTS
CONCERNING INSTALLATION OF FACTORY BUILT
FIREPLACES. Select location for fireplace by taking
into consideration factors previously outlined in
“Choosing the Location.”
FRAMING FIREBOX
Width of framed opening must be as shown in the
adjacent figures.
Entire fireplace can be elevated above floor to
achieve a raised hearth effect. This can be done by
adding a small platform to achieve desired height.
NOTE: Wiring for lower blower must be installed during
framing stage. Insulation should be used in framing
on back, sides, and top.
INSTALL FIREBOX
Install firebox into framed opening by placing it
directly in front of opening and sliding it into proper
position. Please follow wooden surround instructions.
(Also see Zero Clearance standoff(s) Assembly”
section of this manual)
LEVEL FIREBOX
Check level of the firebox on top edge of fireplace
face. Shim if necessary.
COMBUSTIBLE MATERIALS MUST NOT BE INSTALLED
OVER OR TOUCH ANY BLACK PAINTED SURFACE. DO
NOT BLOCK HEAT CIRCULATING AIR OUTLETS. DOING
SO MAY RESULT IN POTENTIAL FIRE HAZARDS.
1. Sidewall Clearances: Clearances from side of
fireplace opening to any adjacent combustible
must be as shown in the figures below.
2. Ceiling Clearances: There is a minimum clearance
from the top of the unit to the ceiling that must
be as shown in the figures below.
WARNING: INSTALLATION AND REPAIRS SHOULD BE PERFORMED BY A QUALIFIED SERVICE
PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY
A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO
EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, PET HAIR, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF APPLIANCE
BE KEPT CLEAN.
13-3/4”
25-1/8”
24” MIN.
CLEARANCE
TO CEILING
SIDE
VIEW
FRONT
VIEW
FRAMING
HEADER
25-1/8”
13-3/4”
25-1/8”
24” MIN.
CLEARANCE
TO CEILING
SIDE
VIEW
FRONT
VIEW
FRAMING
HEADER
25-1/8”