2.3
OPERATION OF CONTROL PANEL
Even when system is in normal condition it constantly or at regular intervals, monitors some
functions to make its sure that panel is in fully operating condition all the time. Some functions are
illustrated below :
•
Monitors all devices and Panel Circuits to check for valid replies, alarms, faults, circuit
integrity, and supervisory or linkage signals
•
Keep refreshing the display and time
•
Monitors power supply troubles and batteries
•
Check/test system memory
•
Monitors for CPU failure
•
Scanning the panel display and for any entries
2.3.1
Event Condition
When the panel detects an event and the information is displayed on-screen in the specific
window. At the same moment the event is recorded in the history. Panel will make sound on
receiving the event which can be silenced using silence soft key on the panel. This action will
silence the alarm however the LEDs will change from flashing to steady for the event and silence.
If the panel is networked, it will send signal to network panel. Silence key acknowledge the event.
Silencing do not affect new event. If there is new event occurs during silence period, panel will
sound the alarm again.
2.3.2
Fire Alarm Event
When the panel receives signal from any detector or monitor modules ( initiating devices ),
following functions are performed by panel :
•
Produce alarm at the panel
•
Activates the System Alarm relay for fire routing device
•
Flashes
‘Red’
Fire LED
•
Displays the Alarm condition on the screen in the
Fire Window
with the description of the
location and complete address of the device
•
Starts delay time, if configured, for control devices
•
Activates the general alarm in the specific zone
•
Sends alarm message to history , printer and repeater ( annunciator panel), if installed
Содержание Addressable Fire Alarm Control Panel
Страница 32: ...ASENWARE LTD 32 Figure 3 10 TCP IP Address Window Screen Figure 3 11 CAN Window Screen ...
Страница 37: ...37 Figure 3 17 User List Figure 3 18 User Access Chart ...
Страница 50: ...50 ASENWARE LTD All dimensions are in mm ...
Страница 52: ...52 ASENWARE LTD All dimensions are in mm Same size of box is supplied for all type of modules ...
Страница 54: ...54 ASENWARE LTD Wiring Connection ...
Страница 56: ...56 ASENWARE LTD Wiring Connection ...
Страница 58: ...58 ASENWARE LTD Wiring Connection ...
Страница 62: ...62 ASENWARE LTD All dimensions are in mm ...
Страница 66: ......