ASENWARE LTD.
29
zone in ‘Location’ and FireQty can be selected up to three devices to avoid false alarm as shown
in Figure 3.7. User can select the number of devices required to allow the panel to send output
signal to Notification Devices in the specific zone.
Delay time for the particular zone can be set up to 10 minutes with maximum 60 seconds of
interval, refer Figure 3.8 (A) and (B).
There are options to override or abort the the zone fire signal, refer Figure 3.6. If panel
received the signal from the device, and user find out if this is real fire, then user need not to wait
until delay time over, in this case he can press
Override
soft touch key. And if user find out that
its a false alarm, during delay time, user can abort the system using
Abort
soft touch key.
Zone testing and zone isolation is possible using ON/OFF slide switch button. Complete
zone can be tested and disabled and it will be notified in the previous window as shown in Figure
3.5. Table 3.1 shows brief summery of zone actions functions.
Figure 3.7 Setting the Fire Qty
Table 3.1 Zone Actions
ACTION
DESCRIPTION
NOTIFICATION
Delay Time
Can be set up to maximum 10 min
It will appear on Zone Settings window
Delay Actions
Override to avoid delay time during real fire Appear on Home screen in General
Window as well as in Zone setting
window
Abort to call off the in case of false alarm
Zone Testing
Individual Zone testing
Appear on Home screen in General
Window and in zone settings it will show
its status
Disablement
Individual Zone disablement or isolation
Содержание Addressable Fire Alarm Control Panel
Страница 32: ...ASENWARE LTD 32 Figure 3 10 TCP IP Address Window Screen Figure 3 11 CAN Window Screen ...
Страница 37: ...37 Figure 3 17 User List Figure 3 18 User Access Chart ...
Страница 50: ...50 ASENWARE LTD All dimensions are in mm ...
Страница 52: ...52 ASENWARE LTD All dimensions are in mm Same size of box is supplied for all type of modules ...
Страница 54: ...54 ASENWARE LTD Wiring Connection ...
Страница 56: ...56 ASENWARE LTD Wiring Connection ...
Страница 58: ...58 ASENWARE LTD Wiring Connection ...
Страница 62: ...62 ASENWARE LTD All dimensions are in mm ...
Страница 66: ......