Return to Normal / Low / Very Low Event Settings
These options display submenus where the event action settings can be configured for each event level.
SiteBoss 571 - Total Power Factor Event Settings for AC Power Monitor 1
A) Low Event Value [0.85]
B) Low Event Actions []
C) Low Event Trap Number [540]
D) Low Event Class [Info]
Low / Very Low Event Value
These fields are used to set the Power Factor settings which trigger the Event Actions. The range is 0.0 to 1.0.
The default is 0.85 for low and 0.70 for very low event.
Return to Normal / Low / Very Low Event Actions
These fields are used to set the action(s) that will be triggered when the Power Factor crosses the set threshold.
This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have
been configured. Refer to
Return to Normal / Low / Very Low Event Trap Number
These fields are used to set the trap number which can be useful when using SNMP trap managers that employ a
trap numbering system to help identify incoming traps. The default trap number for all Average Current Events is
540, but any number in the alternate range of 1000
– 1199 can be used.
Return to Normal / Low / Very Low Event Class
These fields are used to set the class for the event. When this option is selected, a list of the classes previously
defined in the
is displayed. Select one to be assigned to this event. The default is Info.
System Reporting Settings
The System Reporting Settings are not functional.
Disconnect Event Settings
The disconnect event is triggered if communication with the AC power monitor device fails for one minute. The
return to normal event is triggered upon the first subsequent successful communication attempt.
SiteBoss 571 - Disconnect Event Settings for AC Power Monitor 1
A) Event Enabled [OFF]
B) Event Actions []
C) Event Trap Number [524]
D) Event Class [Info]
E) Normal Actions []
F) Normal Trap Number [524]
G) Normal Class [Info]
Event Enable
This is an ON/OFF toggle to enable the Disconnect Event. The default setting is OFF
Event / Normal Actions
Set the action(s) that will be triggered when the AC power monitor fails. This field will be empty [ ] if no actions
have been configured, and will show [*SET*] if one or more actions have been configured. Refer to
more information.
Event / Normal Trap Number
Set the trap number which can be useful when using SNMP trap managers that employ a trap numbering system
to help identify incoming traps. The default trap number for all Disconnect Events is 524, but any number in the
alternate range of 1000
– 1199 can be used.