Ascon Tecnologic - K__V - Indicators -  ENGINEERING MANUAL - PAG. 5

3.6  Power Supply

1

2
3

K31

K38

K48

K85

7
8

1
2

13
14

Supply voltage:   

• 12 VAC/DC (±10%)

 

  

• 24 VAC/DC (±10%);

 

 

 

• 100... 240 VAC (±10%).

Power Consumption:

  5 VA max.

Notes: 1. 

Before connecting the instrument to the power 
line, make sure that line voltage is equal to the 
voltage shown on the identification label;

2. 

To avoid electrical shock, connect power line at 
the end of the wiring procedure.

3. 

For supply connections use No 16 AWG or larger 

wires rated for at last 75 °C.

4. 

Use copper conductors only.

5. 

For power supply the polarity is a do not care 
condition.

6. 

The power supply input is NOT fuse protected.

7. 

Please, provide a T type 1A, 250 V external fuse.

4.  TECHNICAL CHARACTERISTICS

4.1  Technical Specifications

Case:

 Plastic, self-extinguishing degree: V-0 according to UL 94;

Front protection: 

IP 65 (when the optional panel gasket is 

mounted) for indoor locations according to EN 60070-1.

Rear terminals protection:

 IP 20 according to EN 60070-1.

Terminal block:

 Screw terminals (screw M3, for cables of 

0.25... 2.5 mm

2

 or from AWG 22 to AWG 14) with connection 

diagrams.

Dimensions:

 

K3xV:

 78 x 35 x 64  mm (3.07 x 1.38 x 2.52”) 

K4xV:

 48 x 48 x 98 mm (1.77 x 1.77 x 3.86”) 

K85V:

 70 x 84 x 60 mm (2.76 x 3.31 x 2.37”);

Mount cut-out: 
K3xV: 

71

(+0.6)

 x 29

(+0.6)

 mm [2.8

(+0.023)

 x 1.78

(+0.023)

 in.]; 

K4xV:

 45

(+0.6)

 x 45

(+0.6)

 mm [1.78

(+0.023)

 x 1.78

(+0.023)

 in.]; 

K85V:

 DIN rail mounting.

Weight: 

About

 

180 g;

Power Supply:

 

12 VAC/DC (±10% of the nominal voltage);

 

24 VAC/DC (±10% of the nominal voltage);

 

100... 240 VAC (-15... +10% of the nominal voltage);

Power consumption:

 5 VA max.;

Insulation voltage:

 2300 V rms according to EN 61010-1;

Display:

 

One 4 digits red display h 12 mm + 3 LED Bargraph;

Display updating time:

 500 ms;

Sampling time: 130 ms;
Resolution: 30000 counts;

Total Accuracy:

 ±0.5% F.S.V. ±1 digit @ 25°C of room 

temperature;

Common mode rejection:

 120 dB at 50/60 Hz;

Normal mode rejection:

 60 dB at 50/60 Hz;

Electromagnetic compatibility and  
safety requirements

Compliance:

 

- directive EMC 2004/108/CE (EN 61326-1), 

 

- directive LV 2006/95/CE (EN 61010-1);

Installation category:

 II;

Pollution category:

 2;

Temperature drift:

 It is part of the global accuracy;

Operating temperature:

 0... 50°C (32... 122°F);

Storage temperature:

 -30... +70°C (-22... 158°F);

Humidity:

 20... 85% RH, non condensing;

Protections: 

WATCH DOG (hardware/software) for the 

automatic restart.

Содержание 3 V Series

Страница 1: ...1 2 3 4 5 6 7 8 9 10 11 12 Prg Out1 Out2 Out3 70 27 21 12 84 45 60 2 CONNECTIONS 2 1 Connection Diagrams 2 1 1 K31 V Series 1 2 3 4 5 6 12 11 10 9 8 7 13 14 15 16 17 18 19 24 22 21 20 23 OUT4 O UT3 O...

Страница 2: ...ith the instrument specifications 20 to 85 Lo strumento pu essere montato su un pannello con uno spessore massimo di 15 mm Per ottenere la massima protezione frontale IP65 neces sario montare la guarn...

Страница 3: ...hort circuit Internal auxiliary PWS 10 VDC 10 20 mA max 3 3 Output Safety notes To avoid electrical shock connect power line at last For supply connections use No 16 AWG or larger wires rated for at l...

Страница 4: ...ables Use an external dry contact capable to switch 0 5 mA 5 VDC The instrument needs 150 ms to recognize a contact sta tus variation The logic inputs are NOT isolated by the measuring input A double...

Страница 5: ...5 mm2 or from AWG 22 to AWG 14 with connection diagrams Dimensions K3xV 78 x 35 x 64 mm 3 07 x 1 38 x 2 52 K4xV 48 x 48 x 98 mm 1 77 x 1 77 x 3 86 K85V 70 x 84 x 60 mm 2 76 x 3 31 x 2 37 Mount cut out...

Страница 6: ...Output 1 R Relay SPDT 8A AC1 resistive load O VDC for SSR Output 2 Not available R Relay SPDT 8A AC1 resistive load O VDC for SSR 5 3 K48V Model K48V Front panel mounting Indicator 48 x 48 mm Power S...

Страница 7: ...030 It is always possible to end manually the parameter configuration procedure see the next paragraph 3 During parameter modification the instrument con tinue to perform the control In certain condit...

Страница 8: ...lable Always Range When 2 SenS Linear input 0 to 3 When 2 SenS different from linear input 0 or 1 Note Every change of the dP parameter setting will produce a change of the parameters related with it...

Страница 9: ...output repeats the digital input 1 status diF 2 The output repeats the digital input 2 status Notes 1 When two or more outputs are programmed in the same way these outputs will be driven in parallel 2...

Страница 10: ...bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range burn out Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates...

Страница 11: ...arm 23 AL1t HiAb Absolute high alarm 23 AL1t LodE Deviation low alarm relative 23 AL1t LidE Deviation high alarm relative Range From 25 AL1L to 26 AL1H E U 28 HAL1 Alarm 1 hysteresis Available When 23...

Страница 12: ...arm it is the high alarm threshold Available When 30 AL3t is different from nonE or 39 AL3t is different from SE br Range From 41 AL3L to 9999 E U 43 AL3 Alarm 3 threshold Available When 39 AL3t LoAb...

Страница 13: ...mmetrical oscillator with start in ON Start OUT ON off Tr t2 off Tr t1 Tr t1 Tr t2 off Tr t1 Tr t2 Reset ON ON Notes 1 The instrument can receive the start hold and reset commands by U button by logic...

Страница 14: ...push the button The display will show zero and the new readout range becomes 30 70 r P0P For the instruments with normalized signals input it is possible to set the zero value and contemporarily re se...

Страница 15: ...P and AH P is equal to 10 Engineering Units 72 AL o Adjust Low Offset Available Always Range From 300 to 300 E U Example Environmental chamber with an operative range from 10 to 100 C 1 Insert in the...

Страница 16: ...w alternately PASS and 0 3 By and button set a password equal to 81 4 Push button The instrument will show the acronym of the first configu ration parameter group inP 5 By button select the group of t...

Страница 17: ...button in order to memorize the new value and go to the next parameter 8 When you want to come back to the standard display push the button for more than 5 seconds 8 3 How to see but not modify the Li...

Страница 18: ...nt has to be equipped with additional safety devices 10 2 Warranty and Repairs This product is under warranty against manufacturing de fects or faulty materials that are found within 18 months from de...

Страница 19: ...store a complete instrument configuration and to use it for other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer from a PC to an instrume...

Страница 20: ...d Peaks reset t rHr Timer Run Hold Reset transition t run Timer Run transition t rES Timer reset transition t rH Timer run hold Status uP du Digital inputs in parallel to the and keys OFF A 13 diF2 Di...

Страница 21: ...lure indicator bo PF Out of range burn out and Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates the digital input 2 status AL A 24 11 o4AL Alarms...

Страница 22: ...4 Acknowledgeable alarm 0 C 0 31 AL3L For High and low alarms is the low limit of the AL3 threshold For band alarm it is low alarm threshold dP 1999 AL3H E U 1999 C 0 32 AL3H For High and low alarms i...

Страница 23: ...Interface Configuration no Param Description Dec Point Values Default Vis promo 50 PAS2 Password level 2 0 From 0 oFF to 999 oFF Level 2 not protected by psw 20 A 93 51 PAS3 Password level 3 0 From 3...

Страница 24: ...ours nonE A 97 58 h Job Threshold of the worked hours days 0 From 0 oFF to 9999 days hours oFF A 100 CAL Group User Calibration Parameters Configuration no Param Description Dec Point Values Default V...