Ascon Tecnologic - KxxV - Indicators - ENGINEERING MANUAL -V2.0 PAG. 20
Appendix A
]
inp Group - Main and Auxiliary Input Configuration
no. Param.
Description
Dec.
Point
Values
Default
Vis.
promo
HcFG
Parameter available by serial link
shows the current hardware
0
TC/RTD
TC/PTC
Current
Voltage
Accord-
ing to
HW
Not dis-
played
SEnS
Sensor selection (according to the hw
A4
nTC, Pt100 input
0
J, crAL, S, r, t, ir.J, ir.cA, Pt1, 0... 50 (mV), 0... 60 (mV), 12... 60 (mV)
J
TC, PTC, NTC input
J, crAL, S, r, t, Ir.J, Ir.cA, Ptc, ntc, 0... 50 (mV), 0... 60 (mV), 12... 60 (mV) Ptc
I input
0... 20 (mA), 4... 20 (mA)
4... 20
V input
0... 5 (V), 1... 5 (V), 0... 10 (V), 2... 10 (V), 0... 1 (V)
0... 10
dP
Decimal figures
0
0... 3
0
SSc
Initial scale readout
dP
-1999... FSC (E.U.)
-1999
FSc
Final scale readout
dP
SSc... 9999 (E.U.)
9999
0.Pot
Offset value (to shift the zero readout) 1
SSc... FSc (E.U.)
9999
unit
Engineering unit
0
°C o °F
0 = °C
FiL
Digital filter on the measured value
1
0 (oFF)... 20.0 (s)
1.0
diF1
Digital input 1 function
0
oFF = No function;
AAC = Alarm Reset;
ASi = Alarm acknowledge (ACK);
HoLd = Hold of the measured value;
r.Pic = Peaks reset;
0.Pot = Start of the 0.Pot procedure;
r.PoP = Start of the 0.Pot procedure and Peaks reset;
t.rHr = Timer Run/Hold/Reset [transition];
t.run = Timer Run [transition];
t.rES = Timer reset [transition];
t.rH = Timer run/hold [Status];
uP.du = Digital inputs in parallel to the
and
keys
OFF
A-13
diF2
Digital input 2 function
0
A-14
]
Out Group - Output Configuration
no. Param.
Description
Dec.
Point
Values
Default
Vis.
promo
1
o1F
Out 1 function
0
nonE = Output not used.
AL = Alarm output
t.out = Timer output
t.HoF = Tiemer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
diF.1 = The output repeates the digital input 1 status
diF.2 = The output repeates the digital input 2 status
H.reg
A-16
2
o1AL
Alarms linked up with out
0
from 0 to 15
+1 = Alarm 1
+2 = Alarm 2
+4 = Alarm 3
+8 = Alarm 4
+16 = Sensor break (burn out)
AL1
A-17
3
o1Ac
Out 1 action
0
dir = Direct action
rEU = Reverse action
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
dir
C-0
4
o2F
Out 2 function
0
nonE = Output not used.
AL = Alarm output
t.out = Timer output
t.HoF = Tiemer out - OFF in Hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
diF.1 = The output repeates the digital input 1 status
diF.2 = The output repeates the digital input 2 status
AL
A-19