Ascon Tecnologic - K__V - Indicators  -  ENGINEERING MANUAL  -  PAG. 18

9.  ERROR MESSAGES

9.1  Out of Range Signals

The display shows the OVER-RANGE and UNDER-RANGE 
conditions with the following indications:

Over-range Under-range

The sensor break will be signalled as an out of range:

Note: 

When an over-range or an under-range is detected, 
the alarms operate as in presence of the maximum or 
the minimum measurable value respectively.

To check the out of span Error condition, proceed as follows:

1. 

Check the input signal source and the connecting line.

2. 

Make sure that the input signal is in accordance with the 
instrument configuration.
Otherwise, modify the input configuration (see section 4).

3. 

If no error is detected, send the instrument to your sup-
plier to be checked.

9.2  List of Possible Errors

ErEP

  Possible problem of the instrument memory.  The 

messages desappears automatically.  If the error con-
tinues, send the instrument to your supplier.

10. GENERAL NOTES

10.1 Proper use

Every possible use not described in this manual must be 
consider as a improper use.
This instrument is compliant to EN 61010-1 “Safety requirements 
for electrical equipment for measurement, control and laboratory 
use”; for this reason it cannot be used as a safety device.
Ascon Tecnologic S.r.l. and its legal representatives do not 
assume any responsibility for any damage to people, things 
or animals deriving from violation, wrong or improper use or 
in any case not in compliance with the instrument’s features.

D

D

Whenever a failure or a malfunction of the control 
device may cause dangerous situations for persons, 
thing or animals, please remember that the plant has 
to be equipped with additional safety devices.

10.2 Warranty and Repairs

This product is under warranty against manufacturing de-
fects or faulty materials that are found within 18 months from 
delivery date.  The warranty is limited to repairs or to the 
replacement of the instrument.
The tampering of the instrument or an improper use of the 
product will bring about the immediate withdrawal of the 
warranty effects.
In the event of a faulty instrument, either within the period of 
warrantee, or further to its expiry, please contact our sales 
department to obtain authorisation for sending the instru-
ment to our company.  The faulty product must be shipped 
to Ascon Tecnologic with a detailed description of the faults 
found, without any fees or charge for Ascon Tecnologic, 
except in the event of alternative agreements.

10.3 Maintenance

This instrument does not requires periodical recalibration and 
it have no consumable parts so that no particular maintenan-
ce is required. Some times, a cleaning action is suggestable.

1.  SWITCH OFF THE EQUIPMENT

 (power supply, relay 

out, etc.).

2. 

Take the instrument out of its case.

3. 

Using a vacuum cleaner or a compressed air jet (max.  
3 kg/cm

2

) remove all deposits of dust and dirt which may 

be present on the louvers and on the internal circuits 
being careful not to damage the electronic components.

4. 

To clean external plastic or rubber parts use only a cloth 
moistened with:
- Ethyl Alcohol (pure or denatured) [C

2

H

5

OH] or

- Isopropyl Alcohol (pure or denatured) [(CH

3

)

2

CHOH] or

- Water (H

2

O).

5. 

Make sure that there are no loose terminals.

6. 

Before putting the instrument back in its case, make sure 
that it is perfectly dry.

7. 

Put the instrument back and turn it ON.

10.4 Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

Содержание 3 V Series

Страница 1: ...1 2 3 4 5 6 7 8 9 10 11 12 Prg Out1 Out2 Out3 70 27 21 12 84 45 60 2 CONNECTIONS 2 1 Connection Diagrams 2 1 1 K31 V Series 1 2 3 4 5 6 12 11 10 9 8 7 13 14 15 16 17 18 19 24 22 21 20 23 OUT4 O UT3 O...

Страница 2: ...ith the instrument specifications 20 to 85 Lo strumento pu essere montato su un pannello con uno spessore massimo di 15 mm Per ottenere la massima protezione frontale IP65 neces sario montare la guarn...

Страница 3: ...hort circuit Internal auxiliary PWS 10 VDC 10 20 mA max 3 3 Output Safety notes To avoid electrical shock connect power line at last For supply connections use No 16 AWG or larger wires rated for at l...

Страница 4: ...ables Use an external dry contact capable to switch 0 5 mA 5 VDC The instrument needs 150 ms to recognize a contact sta tus variation The logic inputs are NOT isolated by the measuring input A double...

Страница 5: ...5 mm2 or from AWG 22 to AWG 14 with connection diagrams Dimensions K3xV 78 x 35 x 64 mm 3 07 x 1 38 x 2 52 K4xV 48 x 48 x 98 mm 1 77 x 1 77 x 3 86 K85V 70 x 84 x 60 mm 2 76 x 3 31 x 2 37 Mount cut out...

Страница 6: ...Output 1 R Relay SPDT 8A AC1 resistive load O VDC for SSR Output 2 Not available R Relay SPDT 8A AC1 resistive load O VDC for SSR 5 3 K48V Model K48V Front panel mounting Indicator 48 x 48 mm Power S...

Страница 7: ...030 It is always possible to end manually the parameter configuration procedure see the next paragraph 3 During parameter modification the instrument con tinue to perform the control In certain condit...

Страница 8: ...lable Always Range When 2 SenS Linear input 0 to 3 When 2 SenS different from linear input 0 or 1 Note Every change of the dP parameter setting will produce a change of the parameters related with it...

Страница 9: ...output repeats the digital input 1 status diF 2 The output repeats the digital input 2 status Notes 1 When two or more outputs are programmed in the same way these outputs will be driven in parallel 2...

Страница 10: ...bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range burn out Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates...

Страница 11: ...arm 23 AL1t HiAb Absolute high alarm 23 AL1t LodE Deviation low alarm relative 23 AL1t LidE Deviation high alarm relative Range From 25 AL1L to 26 AL1H E U 28 HAL1 Alarm 1 hysteresis Available When 23...

Страница 12: ...arm it is the high alarm threshold Available When 30 AL3t is different from nonE or 39 AL3t is different from SE br Range From 41 AL3L to 9999 E U 43 AL3 Alarm 3 threshold Available When 39 AL3t LoAb...

Страница 13: ...mmetrical oscillator with start in ON Start OUT ON off Tr t2 off Tr t1 Tr t1 Tr t2 off Tr t1 Tr t2 Reset ON ON Notes 1 The instrument can receive the start hold and reset commands by U button by logic...

Страница 14: ...push the button The display will show zero and the new readout range becomes 30 70 r P0P For the instruments with normalized signals input it is possible to set the zero value and contemporarily re se...

Страница 15: ...P and AH P is equal to 10 Engineering Units 72 AL o Adjust Low Offset Available Always Range From 300 to 300 E U Example Environmental chamber with an operative range from 10 to 100 C 1 Insert in the...

Страница 16: ...w alternately PASS and 0 3 By and button set a password equal to 81 4 Push button The instrument will show the acronym of the first configu ration parameter group inP 5 By button select the group of t...

Страница 17: ...button in order to memorize the new value and go to the next parameter 8 When you want to come back to the standard display push the button for more than 5 seconds 8 3 How to see but not modify the Li...

Страница 18: ...nt has to be equipped with additional safety devices 10 2 Warranty and Repairs This product is under warranty against manufacturing de fects or faulty materials that are found within 18 months from de...

Страница 19: ...store a complete instrument configuration and to use it for other instruments To transfer a complete instrument configuration to a PC or from a PC to an instrument To transfer from a PC to an instrume...

Страница 20: ...d Peaks reset t rHr Timer Run Hold Reset transition t run Timer Run transition t rES Timer reset transition t rH Timer run hold Status uP du Digital inputs in parallel to the and keys OFF A 13 diF2 Di...

Страница 21: ...lure indicator bo PF Out of range burn out and Power failure indicator diF 1 The output repeates the digital input 1 status diF 2 The output repeates the digital input 2 status AL A 24 11 o4AL Alarms...

Страница 22: ...4 Acknowledgeable alarm 0 C 0 31 AL3L For High and low alarms is the low limit of the AL3 threshold For band alarm it is low alarm threshold dP 1999 AL3H E U 1999 C 0 32 AL3H For High and low alarms i...

Страница 23: ...Interface Configuration no Param Description Dec Point Values Default Vis promo 50 PAS2 Password level 2 0 From 0 oFF to 999 oFF Level 2 not protected by psw 20 A 93 51 PAS3 Password level 3 0 From 3...

Страница 24: ...ours nonE A 97 58 h Job Threshold of the worked hours days 0 From 0 oFF to 9999 days hours oFF A 100 CAL Group User Calibration Parameters Configuration no Param Description Dec Point Values Default V...

Отзывы: