COn Group - Consumption Parameters Configuration
no. Param.
Description
Dec.
Point
Values
Default
Vis.
promo
57 co.ty
Measurement type
0
oFF = Not used
dAY = Total worked days
Hour = Total worked hours
nonE
A-97
58 h.Job
Threshold of the worked hours/days
0
From 0 (oFF) to 9999 (days/hours)
oFF
A-100
]
CAL Group - User Calibration Parameters Configuration
no. Param.
Description
Dec.
Point
Values
Default
Vis.
promo
59 A.L.P
Adjust low Point
dP
From -1999 to AH.P-10 (E.U.)
0
A-9
60 A.L.o
Adjust low Offset
dP
From -300 to 300 (E.U.)
0
A-10
61 A.H.P
Adjust High Point
dP
From A.L.P +10 to 9999 (E.U.)
9999
A-11
62 A.H.o
Adjust High Offset
dP
From -300 to 300 (E.U.)
0
A-12