Installation and Operation Manual
UPAC- Unite Packet for Messaging and Alarm
18
4.5
Input/Output Setup
Inputs and outputs are defined in the
I/O Setup
page found in the left menu under “Other
Settings”. The activation of an input can be set to “on opening” or “on closing” and the
initial state for the output can be set to “low” or “high”.
Figure 14. I/O Setup page
For the outputs, the state is set to the opposite of the initial state when activated. For
example, if output 2 is set to low in initial state, the output will automatically be set to
high when activated.
Every time a new output or input is defined an automatic ID is created. The ID is a running
number which can manually be changed into another number or a text if wanted. When
an output or input has been deleted, the UPAC will not remember that the previous ID
number is free to be used again. The numbering will just continue on the number after the
last created one.
4.5.1
Defining Inputs and Outputs
Before an input or output can be used in the configuration, it has to be defined with a
name and address.
UPAC inputs
The UPAC hardware has two inputs that can be used. These inputs are predefined at
delivery. The states that can be detected are open and close.
Figure 26.