3--15
Initial Set up
Device 86 Configuration
The Device 86 feature, when enabled, latches output relay 1 closed
whenever any setpoint configured to output relay 1 is tripped. The latch is
only released by a user acknowledgement which can only occur if the
condition causing the trip has met reset conditions. Device 86 is reset by the
user at the Device 86 status screen on top level of display (see page 4–1).
The Device 86 configuration screen allows the user to enable or disable the
feature.
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< SETTINGS >>>
Enable Device 86 ? NO
Clear Setup Log? NO
Press left & right
arrow keys until
Device 86
setup
location appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<<< SETTINGS >>>
Enable Device 86 ?
NO
The word
NO
is blinking.
6
<<< SETTINGS >>>
Enable Device 86 ?
YES
Press up or down
arrow keys
to change
the setting.
7
<<< SETTINGS >>>
Enable Device 86 ? YES
Saves the set-
tings. Nothing is
blinking.
Now press the
Esc
key to return to the top level display.