If incorrect password is
entered you will see;
Invalid Password
Select system nominal
KW capacity
(range: 0 – 24999 KW)
to be used for setpoint
parameters only;
continued on next page.
3--2 Initial Set up
Type of Electrical System
and Source to Monitor
Select one electrical system type and one source to monitor as follows:
Electrical System Type
Source to be Monitored
S
3Ø – 4 Wire WYE
S
Normal
S
3Ø – 3 Wire Delta
S
Emergency
S
1Ø – 3 Wire
S
Load
S
1Ø – 2 Wire
S
Other
The transfer switch position indicating auxiliary contact (Feature 14A) must be connected to the
Power Manager for proper operation (page 2–2). If not, select
Other
for
Source
to be monitored.
!
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
This is the
system type and
source setup
location.
3
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
4
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
System type
is blinking.
5
<<< SETTINGS >>>
System: 3
f
–3W Delta
Source: LOAD
KW Capacity:
0 KW
Press up & down
arrow keys until
correct system
type is selected.
6
<<< SETTINGS >>>
System: 3
f
–3W Delta
Source: LOAD
KW Capacity:
0 KW
Source is
blinking.
7
<<< SETTINGS >>>
System: 3
f
–3W Delta
Source: NORMAL
KW Capacity:
0 KW
Press up & down
arrow keys until
correct source
is selected.
8
<<< SETTINGS >>>
System: 3
f
–3W Delta
Source: NORMAL
KW Capacity: 0 KW
KW Capacity is
blinking.