3--4 Initial Set up
Nominal Frequency, Voltage, and Current Settings
Select the nominal system frequency, voltage, and current to be used with
the setpoint calculations as follows:
Nominal Frequency
S
50 or 60 Hz
Nominal Voltage
S
69 – 59999* volts
* Starting from Firmware version
–010
, the unit displayed next to the
Nominal Voltage value is either
VLL
(for Line to Line = Delta) or
VLN
(for Line to Neutral = WYE). The Nominal Voltage value entered
should correspond to the
Electrical System Type
(see page 3–2).
Nominal Current
S
0 – 29999 amperes
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< SETTINGS >>>
Nom.Frequency: 60 Hz
Nom.Voltage:
115 V
Nom.Current:
0 A
Press left & right
arrow keys until
nominal settings
setup appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<<< SETTINGS >>>
Nom.Frequency:
60 Hz
Nom.Voltage:
115 V
Nom.Current:
0 A
Nom. Frequency
is blinking.
6
<<< SETTINGS >>>
Nom.Frequency:
60 Hz
Nom.Voltage:
115 V
Nom.Current:
0 A
Press up & down
arrow keys until
correct frequency
is displayed.
7
<<< SETTINGS >>>
Nom.Frequency: 60 Hz
Nom.Voltage:
115 V
Nom.Current:
0 A
Repeat steps
6 and 7 for Nom.
Voltage and
Nom. Current.
8
<<< SETTINGS >>>
Nom.Frequency: 60 Hz
Nom.Voltage:
115 V
Nom.Current:
0 A
Saves the new
settings. Noth-
ing is blinking.
Now press the
Esc
key to return to the top level display.