3--12 Initial Set up
Reset Maximum Demand Level
The maximum watt demand register stores the largest instantaneous watt
demand value since last power–up or manual reset. Manual reset is accom-
plished by the following procedure:
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output: NOT USED
Press left & right
arrow keys until
the
Clear Max
Demand
location
appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<<< SETTINGS >>>
Clear Max Demand?
NO
Window Size:
15 min.
SP–Output:
NOT USED
The word NO
is blinking.
6
<<< SETTINGS >>>
Clear Max Demand?
YES
Window Size:
15 min.
SP–Output: NOT USED
Press up & down
arrow keys until
the word YES
appears.
7
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output: NOT USED
Clears max
demand to 0.
Changes back
to NO.
8
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15
min.
SP–Output:
NOT USED
Window Size
is blinking.
9
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output:
NOT USED
SP–Output
is blinking.
10
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output:
NOT USED
Saves the new
setting. Nothing
is blinking.
Now press the
Esc
key to return to the top level display.