IPMI Feature Set
ATCA-7540 Installation and Use (6806871A01A)
315
Fail safe in general can recover from scenarios:
Missing or defect boot block
Firmware image has a bad checksum
When the fail safe logic is triggered as a result of the BMC Watchdog timeout, a System
Firmware Progress event is logged as follows:
Sensor Type: 0x0F (System Firmware Progress)
Event Reading Type Code: 0x6F (Sensor Specific)
Event Data Byte 1: 0xA1 (System Firmware Hang)
Event Data Byte 2: 0x00 (CPU instance)
Event Data Byte 3: 0xXX (Failed Boot Bank ID: 0=Bank A; 1=Bank B)
Figure 9-4. Fail Safe Logic Diagram
Sw ap Boot Bank and send
a System Firmw are Hang
event to the ShMM
Start
Send a BMC W atchdog
event to the ShMM
Reboot the blade
Yes
Yes
Yes
W atchdog
expired?
Fail safe enabled?
Fail safe count < 3?