![Arneg Atlanta Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/arneg/atlanta/atlanta_direction-for-installation-and-use_2974521047.webp)
Atlanta
English
05060191 00 06-2021
20
The tempera
-
ture of the
cabinet is too
high or too
low
•
poor room conditions
•
check the position of the cabinet inside the
store chap.13
•
output air temperature is out-
side the specified range
•
check the operation of evaporator fan
•
check wiring and input voltage
•
the fans are installed reversely; check and re-
store the air flow direction
•
check that fan plenum is sufficient and not
obstructed
•
check the intake pressure that should comply
with rated specifications
•
the cabinet is defrosting.
•
check defrosting parameters
•
the capacitor or the evaporator
are freezing.
•
check that the suction line is not obstructed
•
the capacitor or the evaporator
are obstructed or dirty.
•
proceed with cleaning operations see chap.20
•
the load is not distributed even-
ly
•
load the goods in an orderly fashion (Fig.13)
Water leaks,
bad smell
•
the cabinet drains are blocked
or damaged
•
free the drain
•
repair or replace the drains
•
water collection tray is sealed
incorrectly
•
seal it properly
•
water collection tray overflows
•
check wiring of evaporation heater
•
check the operation of evaporation heater
•
insufficient joints between cabi-
nets in channel or joints not
sealed correctly
•
install and seal the joints
Frost or ice
in the cabinet
•
fans do not work
in the evaporator
•
heating elements broken
•
Sdef probe detached
•
check electrical connections
•
air currents that alter the circu-
lation of refrigerated air
•
check the ventilation inside the store
i
In all cases not described or where it is not possible to solve the problem by following these
instructions, call the nearest authorised after-sales centre.